Thermostat wiring diagram, Branch circuit sizing guide, Watt load – State SBV 65 10TS User Manual

Page 16

background image

16

120

V

WATT

LOAD

BRANCH CIRCUIT SIZING GUIDE

Based on N.E.C. NFPA NO. 70 - 1999

208

V

240

V

Recommend

Over Current

Protection Rating

120

V

208

V

240

V

Copper Wire Size

AWG Based on N.E.C.

Table 310 - 16 (60°C)

* Wattages less than 1500 may be wired 14 gage with 15 amp

protection

BLACK

BLACK

L1

L2

FUSED DISCONNECT

OR CIRCUIT BREAKER

RED

THERMOSTAT

&

HIGH LIMIT

CONTROL

WIRING NO. 7

SINGLE ELEMENT HEATER

6603461G

RED

HEATING

ELEMENT

GROUND

SCREW

ELECTRICAL

SERVICE

GROUND

WHITE

BLACK

BLACK

HOT

WHITE

THERMOSTAT

&

HIGH LIMIT

CONTROL

NEUTRAL

FUSED DISCONNECT

OR CIRCUIT BREAKER

WIRING NO. 1

SINGLE ELEMENT HEATER

6603461H

HEATING

ELEMENT

GROUND

SCREW

ELECTRICAL

SERVICE

GROUND

THERMOSTAT WIRING DIAGRAM

1500* 15 15 15 12 14 14

2000 20 15 15 10 14 14

2500 30 15 15 10 14 14

3000 30 20 15 8 12 12

3500

-

20

20

-

10

12

4000

-

25

20

-

10

10

4500

-

30

25

-

10

10

5000

-

30

30

-

10

10

5500

-

35

30

-

8

10

6000

-

35

30

-

8

8

9000

-

50

45

-

6

6

12000

-

70

60

-

3

4

Important: Read and understand the Electrical Requirements section on page 4.