To reduce the risk of excessive pressures and temperatures

in this water heater, install temperature and pressure relief

protective equipment required by local codes, but no less

than a combination temperature and pressure relief valve

certified by a nationally recognized testing laboratory that

maintains periodic inspection of the production of listed

equipment or materials, as meeting the requirements for

Relief Valves and Automatic Shutoff Devices for Hot Water

Supply Systems, ANSI Z21.22 - latest edition. This valve

must be marked with the maximum set pressure not to

exceed the marked maximum working pressure of the

water heater. Install the valve into an opening provided

and marked for this purpose in the water heater, and orient

it or provide tubing so that any discharge from the valve

exits only within 6 inches above drain, or at any distance

below, the structural floor, and does not contact any live

electrical part. The discharge opening must not be blocked

or reduced in size under any circumstance.

IMPORTANT:

Only a new temperature and pressure relief

valve should be used with your water heater. Do not use an

old or existing valve as it may be damaged or not adequate

for the working pressure of the new water heater. Do not

place any valve between the relief valve and the tank.
The Temperature & Pressure Relief Valve:

• Shall not be in contact with any electrical part.
• Shall be connected to an adequate discharge line.
• Shall not be rated higher than the working pressure

shown on the data plate of the water heater.

The Discharge Line:

• Shall not be smaller than the pipe size of the relief

valve or have any reducing coupling installed in the

discharge line.

• Shall not be capped, blocked, plugged or contain

any valve between the relief valve and the end of the

discharge line.

• Shall terminate a maximum of six inches above a floor

drain or external to the building. In cold climates, it is

recommended that the discharge pipe be terminated at

an adequate drain inside the building.

• Shall be of material listed for hot water distribution.
• Shall be installed to allow complete drainage of both

the valve and discharge line.

Temperature/Pressure Relief Valve and

Pipe Insulation

1. Locate the temperature and pressure relief valve on the

water heater (also known as a T&P relief valve). See

Figure 6.

2. Locate the slit running the length of the T&P relief valve

insulation.

3. Spread the slit open and fit the insulation over the T&P

relief valve. See Figure 7. Apply gentle pressure to the

insulation to ensure that it is fully seated on the T&P Re-

lief Valve. Once seated, secure the insulation with duct

tape, electrical tape, or equivalent.

IMPORTANT:

The insulation and tape must not block

the discharge opening or hinder access to the manual

relief lever (Figure 7). Ensure a discharge pipe is in-

stalled into the T&P valve discharge opening per the

instructions in this manual.

Temperature and Pressure

Relief Valve

Explosion Hazard

If the temperature and pressure relief valve

is dripping or leaking, have a qualified

person replace it.
Examples of a qualified person include:

licensed plumbers, authorized electric

company personnel, and authorized service

personnel.
Do not plug valve.
Do not remove valve.
Failure to follow these instructions can

result in death or explosion.

WARNING

6” Maximum

Air Gap

Drain Pan 2 1/2”

Depth Maximum and

2 Inches wider than

the water heater.

Discharge Pipe

(Do Not Plug or Cap)

Temperature and

Pressure Relief Valve

Drain Line 3/4”

ID Minimum

Drain

Figure 6

Temperature and Pressure

Relief Valve Installation

For protection against excessive pressures and

temperatures, a temperature and pressure relief valve must

be installed in the opening marked “T & P RELIEF VALVE”

(See Figure 5).