beautypg.com

Installation checklist, Water heater location, Water system piping – State EPX 80 DHPT User Manual

Page 12: Condensate drain line installation, Electrical connections, Post installation review

background image

12

Water Heater Location

□ Centrally located with the water piping system.

□ The flooring beneath the water heater must be able to

support the weight of the water heater when filled with

water (See Table 1).

□ Located indoors (such as a basement or garage)

and in a vertical position. Sheltered from freezing

temperatures.

□ Provisions made to shelter the area from water

damage. Metal drain pan installed and piped to an

adequate drain.

□ Sufficient room to service the water heater.

□ The water heater must have unrestricted airflow and

requires a minimum installation space of 750 cubic feet.

As an example, a room that has an eight foot tall ceiling

and is 10 feet long by 9-1/2 feet wide would contain

760 cubic feet. See The Confined Space Installation

section of this manual for installing the water heater in

spaces of less than 750 cubic feet.

NOTE: This Heat Pump Water Heater may be located

within a required minimum

of 6” clearance from a wall

on the inlet or outlet side, however for future service

considerations a minimum clearance of 3 feet from

any obstruction on the left and right side (air inlet and

outlet) is recommended.

□ The unit cannot be placed into any type of closet or

small enclosure.

□ The site location must be free from any corrosive

elements in the atmosphere such as sulfur, fluorine,

and chlorine. These elements are found in aerosol

sprays, detergents, bleaches, cleaning solvents, air

fresheners, paint, and varnish removers, refrigerants,

and many other commercial and household products.

In addition excessive dust and lint may affect the

operation of the unit and require more frequent

cleaning (See “Cleaning the Heat Pump” section).

□ Ambient air temperature must be above 45°F and

below 109°F. If the ambient air temperature falls

outside these upper and lower limits the electrical

elements will activate to meet the hot water demand.

Water System Piping

□ Temperature and pressure relief valve properly

installed with a discharge pipe run to an adequate drain

and sheltered from freezing (See Figure 5).

□ All piping properly installed and free of leaks.

□ Heater completely filled with water (See “Water Piping

System” section).

□ Closed system pressure buildup precautions installed

(See “Closed System/Thermal Expansion” section).

INSTALLATION CHECKLIST

□ Mixing valve (when applicable) installed per

manufacturer’s instructions (See “Water Temperature

Regulation” section).

Condensate Drain Line Installation

□ Must be located with access to an adequate drain or

condensate pump.

□ Condensate drain lines installed and piped to an

adequate drain or condensate pump (See Figure 4).

Electrical Connections

□ This water heater requires a 240 VAC single phase 25

amp power supply. DO NOT use a 208 VAC service.

□ Wiring size and connections comply with all applicable

codes or in the absence of local or state codes follow

NFPA-70, the National Electrical Code-current edition.

□ Water heater and electrical supply are properly

grounded.

□ Wiring enclosed in approved conduit (if required by

local codes).

□ Proper overload fuse or circuit breaker protection

installed.

Post Installation Review

□ Understand how to use the User Interface Module to

set the various modes and functions (See “Adjusting

the User Interface Module/Operating Modes” section).

□ Hybrid Mode is the recommended Operating Mode.

Understand the various Operating Modes and which

mode may be best based on season, ambient

temperature, and usage (See “Operating Mode

Description” section).

NOTE: It may be necessary to temporarily change

modes if for example filling a spa or hot tub.

□ Understand the importance of routine inspection/

maintenance of the condensate drain pan and lines

(See “

Inspection/Cleaning of the Condensate Drain

Pan & Condensate Drain Lines” section)

. This is to

help prevent any possible drain line blockage resulting

in the condensate drain pan overflowing.

IMPORTANT: Water coming from the plastic shroud is

an indicator that both condensation drain lines may be

blocked. Immediate action is required.

□ To maintain optimal operation check, remove and clean

the air filter (See “Air Filter Cleaning/Replacement”

section).

□ The Installation Instructions and Use & Care Guide

should be kept with the water heater for reference.

This manual is related to the following products: