beautypg.com

Operation, Table 3 charge controller configuration block – Outback Power Systems AXS Port SunSpec Modbus Interface Owners Manual User Manual

Page 13

background image

Operation

900-0138-01-00 Rev

B

11

Table 3 Charge Controller Configuration Block

Start End Size R/W Name

Type

Units

Scale
Factor Contents

Description

11 11 1 R/W

CCconfig_Absorb_Time_
Hours

uint16 Hours

Hours
_SF

Programmable Absorb Time Hours

12 12 1 R/W

CCconfig_Absorb_End_
Amps uint16

Amps

Voltage
_SF

Programmable Amperage to end Absorbing

13 13 1 R/W

CCconfig_Rebulk_Volts uint16 Volts

Voltage
_SF

Programmable Voltage to re-initiate Bulk charge

14 14 1 R/W

CCconfig_Float_Volts uint16

Volts

Voltage
_SF

Programmable Float Voltage Target

15 15 1 R/W

CCconfig_Bulk_Current uint16 Amps

Voltage
_SF

Programmable Max Output Current Limit

16 16 1 R/W

CCconfig_EQ_Volts

uint16 Volts

Voltage
_SF

Programmable Target Voltage for Equalize

17 17 1 R/W

CCconfig_EQ_Time_Hours

uint16 Hours N/A

Programmable EQ

Time

Hours

18 18 1 R/W

CCconfig_Auto_EQ_Days

uint16

Days

N/A

Programmable Auto EQ Interval Days

19 19 1 R/W

CCconfig_MPPT_Mode

uint16 Enumerated

Descrip
tive

Programmable 0 = Auto; 1 = U-Pick

20 20 1 R/W

CCconfig_Sweep_Width uint16 Enumerated

Descrip
tive

Programmable 0 = Full; 1 = Half

21 21 1 R/W

CCconfig_Sweep_Max_
Percentage

uint16 Enumerated

Descrip
tive

Programmable 0 = 80; 1 = 85; 2 = 90; 3 = 99

22 22 1 R/W

CCconfig_U_Pick_PWM_
Duty_Cycle

uint16 Percentage

Voltage
_SF

Programmable Park Duty Cycle (%)

23 23 1 R/W

CCconfig_Grid_Tie_Mode uint16 Enumerated

Descrip
tive

Programmable

0 = Grid Tie Mode disabled; 1 = Grid Tie Mode
enabled

24 24 1 R/W

CCconfig_Temp_Comp_
Mode

uint16 Enumerated

Descrip
tive

Programmable 0 = Wide; 1 = User Limited

25 25 1 R/W

CCconfig_Temp_Comp_
Lower_Limit_Volts uint16

Volts

Voltage
_SF

Programmable RTS compensation lower voltage limit

26 26 1 R/W

CCconfig_Temp_Comp_
Upper_Limit_Volts

uint16 Volts

Voltage
_SF

Programmable RTS compensation upper voltage limit

27 27 1 R/W

CCconfig_Auto_Restart_
Mode

uint16 Enumerated

Descrip
tive

Programmable

0 = Off; 1 = Restart every 90 minutes; 2 = Restart
every 90 minutes if absorb charging or float charging

28 28 1 R/W

CCconfig_Wakeup_VOC uint16 Volts

Voltage
_SF

Programmable Voc change which causes Wakeup occurs

29 29 1 R/W

CCconfig_Snooze_Mode_
Amps

uint16 Amps

Voltage
_SF

Programmable Snooze Mode Amps

30 30 1 R/W

CCconfig_Wakeup_Interval

uint16

Mins

N/A

Programmable How often to check for Wakeup condition

31 31 1 R/W

CCconfig_AUX_Mode uint16

Enumerated

Descrip
tive Programmable

0 = Float; 1 = Diversion: Relay; 2 = Diversion: Solid St;
3 = Low Batt Disconnect; 4 = Remote; 5 = Vent Fan; 6
= PV Trigger; 7 = Error Output; 8 = Night Light

32 32 1 R/W

CCconfig_AUX_Control uint16 Enumerated

Descrip
tive

Programmable 0 = Off; 1 = On; 2 = Auto

33 33 1 R CCconfig_AUX_State uint16

Enumerated

Descrip
tive

Read Only

0 = Disabled; 1 = Enabled

34 34 1 R/W

CCconfig_AUX_Polarity uint16 Enumerated

Descrip
tive

Programmable 0 = Low; 1 = High

35 35 1 R/W

CCconfig_AUX_Low_Batt_
Disconnect uint16

Volts

Voltage
_SF

Programmable Low Battery Disconnect Voltage

36 36 1 R/W

CCconfig_AUX_Low_Batt_
Reconnect uint16

Volts

Voltage
_SF

Programmable Low Battery Reconnect Volts

37 37 1 R/W

CCconfig_AUX_Low_Batt_
Disconnect_Delay

uint16

Secs

N/A

Programmable Low Battery Disconnect Delay (secs)

38 38 1 R/W

CCconfig_AUX_Vent_Fan_
Volts

uint16 Volts

Voltage
_SF

Programmable Vent Fan Voltage

39 39 1 R/W

CCconfig_AUX_PV_Limit_
Volts

uint16 Volts

Voltage
_SF

Programmable Voltage at which PV disconnect occurs

40 40 1 R/W

CCconfig_AUX_PV_Limit_
Hold_Time

uint16

Secs

N/A

Programmable AUX PV Trigger Hold Time

41 41 1 R/W

CCconfig_AUX_Night_
Light_Thres_Volts uint16

Volts

Voltage
_SF

Programmable Voltage Threshold for AUX Night Light

42 42 1 R/W

CCconfig_Night_Light_
ON_Hours

uint16

Hours

N/A

Programmable Night Light ON Time

43 43 1 R/W

CCconfig_Night_Light_
ON_Hyst_Time

uint16

Secs

N/A

Programmable Night Light ON Hyst Time

44 44 1 R/W

CCconfig_Night_Light_
OFF_Hyst_Time

uint16

Secs

N/A

Programmable Night Light OFF Hyst Time

45 45 1 R/W

CCconfig_AUX_Error_
Battery_Volts uint16

Volts

Voltage
_SF

Programmable Battery voltage at which Aux Error occurs

46 46 1 R/W

CCconfig_AUX_Divert_
Hold_Time uint16

Hours

Voltage
_SF

Programmable AUX Diver Hold Time

47 47 1 R/W

CCconfig_AUX_Divert_
Delay_Time

uint16

Secs

N/A

Programmable AUX Divert Delay