Operation, Table 3 charge controller configuration block – Outback Power Systems AXS Port SunSpec Modbus Interface Owners Manual User Manual
Page 13
Operation
900-0138-01-00 Rev
B
11
Table 3 Charge Controller Configuration Block
Start End Size R/W Name
Type
Units
Scale
Factor Contents
Description
11 11 1 R/W
CCconfig_Absorb_Time_
Hours
uint16 Hours
Hours
_SF
Programmable Absorb Time Hours
12 12 1 R/W
CCconfig_Absorb_End_
Amps uint16
Amps
Voltage
_SF
Programmable Amperage to end Absorbing
13 13 1 R/W
CCconfig_Rebulk_Volts uint16 Volts
Voltage
_SF
Programmable Voltage to re-initiate Bulk charge
14 14 1 R/W
CCconfig_Float_Volts uint16
Volts
Voltage
_SF
Programmable Float Voltage Target
15 15 1 R/W
CCconfig_Bulk_Current uint16 Amps
Voltage
_SF
Programmable Max Output Current Limit
16 16 1 R/W
CCconfig_EQ_Volts
uint16 Volts
Voltage
_SF
Programmable Target Voltage for Equalize
17 17 1 R/W
CCconfig_EQ_Time_Hours
uint16 Hours N/A
Programmable EQ
Time
Hours
18 18 1 R/W
CCconfig_Auto_EQ_Days
uint16
Days
N/A
Programmable Auto EQ Interval Days
19 19 1 R/W
CCconfig_MPPT_Mode
uint16 Enumerated
Descrip
tive
Programmable 0 = Auto; 1 = U-Pick
20 20 1 R/W
CCconfig_Sweep_Width uint16 Enumerated
Descrip
tive
Programmable 0 = Full; 1 = Half
21 21 1 R/W
CCconfig_Sweep_Max_
Percentage
uint16 Enumerated
Descrip
tive
Programmable 0 = 80; 1 = 85; 2 = 90; 3 = 99
22 22 1 R/W
CCconfig_U_Pick_PWM_
Duty_Cycle
uint16 Percentage
Voltage
_SF
Programmable Park Duty Cycle (%)
23 23 1 R/W
CCconfig_Grid_Tie_Mode uint16 Enumerated
Descrip
tive
Programmable
0 = Grid Tie Mode disabled; 1 = Grid Tie Mode
enabled
24 24 1 R/W
CCconfig_Temp_Comp_
Mode
uint16 Enumerated
Descrip
tive
Programmable 0 = Wide; 1 = User Limited
25 25 1 R/W
CCconfig_Temp_Comp_
Lower_Limit_Volts uint16
Volts
Voltage
_SF
Programmable RTS compensation lower voltage limit
26 26 1 R/W
CCconfig_Temp_Comp_
Upper_Limit_Volts
uint16 Volts
Voltage
_SF
Programmable RTS compensation upper voltage limit
27 27 1 R/W
CCconfig_Auto_Restart_
Mode
uint16 Enumerated
Descrip
tive
Programmable
0 = Off; 1 = Restart every 90 minutes; 2 = Restart
every 90 minutes if absorb charging or float charging
28 28 1 R/W
CCconfig_Wakeup_VOC uint16 Volts
Voltage
_SF
Programmable Voc change which causes Wakeup occurs
29 29 1 R/W
CCconfig_Snooze_Mode_
Amps
uint16 Amps
Voltage
_SF
Programmable Snooze Mode Amps
30 30 1 R/W
CCconfig_Wakeup_Interval
uint16
Mins
N/A
Programmable How often to check for Wakeup condition
31 31 1 R/W
CCconfig_AUX_Mode uint16
Enumerated
Descrip
tive Programmable
0 = Float; 1 = Diversion: Relay; 2 = Diversion: Solid St;
3 = Low Batt Disconnect; 4 = Remote; 5 = Vent Fan; 6
= PV Trigger; 7 = Error Output; 8 = Night Light
32 32 1 R/W
CCconfig_AUX_Control uint16 Enumerated
Descrip
tive
Programmable 0 = Off; 1 = On; 2 = Auto
33 33 1 R CCconfig_AUX_State uint16
Enumerated
Descrip
tive
Read Only
0 = Disabled; 1 = Enabled
34 34 1 R/W
CCconfig_AUX_Polarity uint16 Enumerated
Descrip
tive
Programmable 0 = Low; 1 = High
35 35 1 R/W
CCconfig_AUX_Low_Batt_
Disconnect uint16
Volts
Voltage
_SF
Programmable Low Battery Disconnect Voltage
36 36 1 R/W
CCconfig_AUX_Low_Batt_
Reconnect uint16
Volts
Voltage
_SF
Programmable Low Battery Reconnect Volts
37 37 1 R/W
CCconfig_AUX_Low_Batt_
Disconnect_Delay
uint16
Secs
N/A
Programmable Low Battery Disconnect Delay (secs)
38 38 1 R/W
CCconfig_AUX_Vent_Fan_
Volts
uint16 Volts
Voltage
_SF
Programmable Vent Fan Voltage
39 39 1 R/W
CCconfig_AUX_PV_Limit_
Volts
uint16 Volts
Voltage
_SF
Programmable Voltage at which PV disconnect occurs
40 40 1 R/W
CCconfig_AUX_PV_Limit_
Hold_Time
uint16
Secs
N/A
Programmable AUX PV Trigger Hold Time
41 41 1 R/W
CCconfig_AUX_Night_
Light_Thres_Volts uint16
Volts
Voltage
_SF
Programmable Voltage Threshold for AUX Night Light
42 42 1 R/W
CCconfig_Night_Light_
ON_Hours
uint16
Hours
N/A
Programmable Night Light ON Time
43 43 1 R/W
CCconfig_Night_Light_
ON_Hyst_Time
uint16
Secs
N/A
Programmable Night Light ON Hyst Time
44 44 1 R/W
CCconfig_Night_Light_
OFF_Hyst_Time
uint16
Secs
N/A
Programmable Night Light OFF Hyst Time
45 45 1 R/W
CCconfig_AUX_Error_
Battery_Volts uint16
Volts
Voltage
_SF
Programmable Battery voltage at which Aux Error occurs
46 46 1 R/W
CCconfig_AUX_Divert_
Hold_Time uint16
Hours
Voltage
_SF
Programmable AUX Diver Hold Time
47 47 1 R/W
CCconfig_AUX_Divert_
Delay_Time
uint16
Secs
N/A
Programmable AUX Divert Delay