beautypg.com

Operation, Table 1 outback block – Outback Power Systems AXS Port SunSpec Modbus Interface Owners Manual User Manual

Page 11

background image

Operation

900-0138-01-00 Rev

B

9

Table 1 OutBack Block

Start End Size R/W Field Name

Type

Units

Scale
Factor Contents

Description

4 4 1 R

OutBack_Minor_Firmware
_Number

uint16

N/A

N/A

Read Only

OutBack Minor firmware revision

5 5 1 R OutBack_Encryption_Key uint16 N/A

N/A Read

Only

Encryption key for current session (0 = Encryption not
enabled)

6 12

7 R OutBack_MAC_Address

String (14)

N/A

N/A

Read Only

Ethernet MAC address

13

20

8

W

OutBack_Write_Password

String (16)

N/A

N/A

Write Only

Password required to write to any register

21 21 1 R/W

OutBack_Enable_DHCP uint16 Enumerated

N/A Programmable

0 = DHCP Disabled, use configured network
parameter; 1 = DHCP Enabled

22 23 2 R/W

OutBack_TCP/IP_Address uint32 Address

N/A

Programmable TCP/IP Address xxx.xxx.xxx.xxx

24 25 2 R/W

OutBack_TCP/IP_Gateway
_MSW

uint32

Address

N/A

Programmable TCP/IP Gateway xxx.xxx.xxx.xxx

26 27 2 R/W

OutBack_TCP/IP_Netmask
_MSW

uint32

Address

N/A

Programmable TCP/IP Netmask xxx.xxx.xxx.xxx

28 29 2 R/W

OutBack_TCP/IP_DNS_1_
MSW

uint32

Address

N/A

Programmable TCP/IP DNS 1 xxx.xxx.xxx.xxx

30 31 2 R/W

OutBack_TCP/IP_DNS_2_
MSW

uint32

Address

N/A

Programmable TCP/IP DNS 2 xxx.xxx.xxx.xxx

32 32 1 R/W

OutBack_Modbus_Port uint16 N/A

N/A Programmable OutBack

MODBUS IP port, default 502

33 52 20 R/W

OutBack_SMTP_Server_
Name

String (40)

N/A

N/A

Programmable Email server name

53 68 16 R/W

OutBack_SMTP_Account_
Name

String (32)

N/A

N/A

Programmable Email account name

69 69 1 R/W

OutBack_SMTP_SSL_
Enable

uint16

Enumerated

N/A

Programmable 0 = SSL Disabled; 1 = SSL Enabled (not implemented)

70 77 8 W

OutBack_SMTP_Email_
Password

String 16)

N/A

N/A

Write Only

Email account password

78 97 20 R/W

OutBack_SMTP_Email_
User_Name

String (40)

N/A

N/A

Programmable Email account User Name

98 98 1 R/W

OutBack_Status_Email_
Interval

uint16 N/A

N/A Programmable

0 = Status Email Disabled, 1-23 Status Email every n
hours

99 99 1 R/W

OutBack_Status_Email_
Status_Time uint16

N/A

N/A

Programmable Hour of first status email of the day

100 124 25 R/W

OutBack_Status_Email_
Subject_Line

String (50)

N/A

N/A

Programmable Status Email Subject Line

125 144 20 R/W

OutBack_Status_Email_To
_Address_1

String (40)

N/A

N/A

Programmable Status Email to Address 1

145 164 20 R/W

OutBack_Status_Email_To
_Address_2

String (40)

N/A

N/A

Programmable Status Email to Address 2

165 165 1 R/W

OutBack_Alarm_Email_
Enable

uint16 Enumerated

N/A Programmable 0 = Disabled; 1 = Enabled

166 190 25 R/W

OutBack_Alarm_Email_
Subject_Line

String (50)

N/A

N/A

Programmable Status Alarm_Subject Line

191 210 20 R/W

OutBack_Alarm_Email_To_
Address_1

String (40)

N/A

N/A

Programmable Status Alarm to Address 1

211 230 20 R/W

OutBack_Alarm_Email_To_
Address_2

String (40)

N/A

N/A

Programmable Status Alarm to Address 2

231 238 8 W OutBack_FTP_Password String

(16)

N/A

N/A Write Only

FTP password

239 246 8 W OutBack_Telnet_Password String

(16)

N/A

N/A

Write

Only

Telnet password (not implemented)

247 247 1 R/W

OutBack_SD_Card_Data_
Log_Write_Interval

uint16 N/A

N/A Programmable 0 = SD-Card Data Logging disabled, 1-60 seconds

248 248 1 R/W

OutBack_SD_Card_Data_
Log_Retain_Days

uint16 N/A

N/A Programmable

0 = Log until SD-Card is full then erase oldest, 1-731
Number of days to retain data logs

249 249 1 R/W

OutBack_SD_Card_Data_
Logging_Mode

uint16

Enumerated

N/A

Programmable 0 = Disabled; 1 = Excel Format; 2 = Compact Format

250 269 20 R/W

OutBack_Time_Server_
Name

String (40)

N/A

N/A

Programmable Timeserver domain name

270 270 1 R/W

OutBack_Enable_Time_
Server

uint16 Enumerated

N/A Programmable

0 = Time Server Disabled, use configured time
parameters; 1 = Time Server Enabled

271 271 1 R/W OutBack_Set_Time_Zone int16

Hours

N/A Programmable Time Zone -12-11

272 272 1 R/W OutBack_Year

uint16 N/A

N/A Programmable Clock year (4 digit)

273 273 1 R/W OutBack_Month

uint16 N/A

N/A Programmable Clock Month (1 - 12)

274 274 1 R/W OutBack_Day

uint16 N/A

N/A Programmable Clock Day (1 - 31)

275 275 1 R/W OutBack_Hour

uint16

N/A

N/A Programmable Clock Hour (0 - 23)

276 276 1 R/W OutBack_Minute

uint16 N/A

N/A Programmable Clock Minute (0 - 59)

277 277 1 R/W OutBack_Second

uint16 N/A

N/A Programmable Clock Second (0 - 59)

278 278 1 R OutBack_Temp_Batt

int16

Degrees

C N/A Measured Battery

temp in degrees C

279 279 1 R OutBack_Temp_Ambient int16 Degrees

C

N/A

Measured

Ambient temp from temp sensor connected to
device, in degrees C

280 280 1 R OutBack_Temp_SF

int16

N/A

N/A

0

Temperature Scale Factor

281 281 1 R OutBack_Error

uint16 Bitfield N/A Read

Only

Bit field for errors. See Table 6 on page 3.

282 282

1 R

OutBack_Status

uint16 Bitfield N/A Read

Only

Bit field for status. TBD.

283 283

1 N/A OutBack_Spare_Register_1 uint16

N/A

N/A

N/A

For future use