Requirements – Outback Power Systems PV 12 Combiner User Manual

Page 7

background image

5

Maximum Fuse Rating

15 AMP , 600VDC

Maximum Circuit Breaker Rating

15 AMP, 150VDC

Total Maximum Current Rating

PV8—120 AMPS DC PV12—180 Amps DC

Maximum Fuse Short Circuit Current

10kA

Maximum Breaker Short Circuit Current

10kA for 80V; 100A for 150V

Requirements


• Use minimum 75

0

C copper conductors.

• Use only code-approved, appropriately listed circuit breakers, fuse holders, and fuses.

Torque Data* for DC Negative Bus Bar Small Holes

WIRE SIZE

TORQUE

AWG

mm

2

in lbs

Nm

14-10

2.1-5.3

20

2.3

8

8.4

25

2.8

6

13.3-21.2

35

4.0

Torque Data* for Box Lug

WIRE SIZE

TORQUE

AWG

mm

2

in lbs

Nm

14-10

2.1-5.3

35

4.0

8

8.4

40

4.5

6-4

13.3-21.2

45

5.1

2/0-3

13.3-21.2

50

5.7

Torque Data* for DC Negative Bus Bar Large Holes

WIRE SIZE

TORQUE

AWG

mm

2

in lbs

Nm

14-10

2.1-5.3

35

4.0

8

8.4

40

4.5

6-4

13.3-21.2

45

5.1

2/0-3

13.3-21.2

50

5.7

Torque Data* for Ground Bus Bar

WIRE SIZE

TORQUE

AWG

mm

2

in lbs

Nm

14-10

2.1-5.3

20

2.3

8

8.4

25

2.8

6-4

13.3-21.2

35

4.o

DIN Rail Mounted Breaker and Fuse Holder Terminals are torqued 22 in lbs/2.5 Nm

*Data is also listed on the product label attached to the combiner box.