Planning

10

900-0144-01-01 Rev A

Maintenance Bypass Switching

Inverter systems are often equipped with AC maintenance bypass switches or interlocks. If the

inverter system ever needs to be shut down or removed, the AC sources and loads must be

disconnected. A bypass device allows the AC source to deliver power directly to the loads, bypassing

the inverter. This can minimize disruption to the system and avoids the need for extensive rewiring.

Figure 4 Bypass Switching

The GS Load Center (GSLC) can be equipped with bypass circuit breakers for this purpose. However, if

multiple Radian inverters are stacked in a single system, then the GSLC bypass kits should not be used.

The bypass function must be simultaneous for all inverters. The GSLC bypass kits operate

independently, not simultaneously.
Both manual and automatic double-throw bypass switches are commonly available in a range of sizes
and options. These are highly recommended for systems with more than a single inverter.

WARNING: Shock Hazard or Equipment Damage

Using independent bypass devices on multiple inverters can result in power being routed to

inappropriate places. This could create an electric shock hazard or damage the equipment.

Figure 5 Bypass Switching for Multiple Inverters

AC Source

AC Loads

GSLC Bypass

Inoperative

Radian

Inverter

Input Wiring

Output Wiring

AC Source

AC Loads

Output Wiring

Inactive Radian Inverters

GSLC Bypass Devices

(not to be used)

External Bypass Device

Input Wiring