Servicing should only be performed by a Qualified Service Agent

VF BOILER SERVICE MANUAL

MCB - SECTION C

The upper right corner of the MCB contains the following sockets/components:

J2 Socket (Pump relay coil; IRI gas valve)

• Pin 1 - 120 VAC switched hot wire to pump relay coil
• Pin 2 - 120 VAC neutral wire to pump relay coil
• Pin 3 - 120 VAC hot wire to IRI gas valve - N/A on VF boilers.
• Pin 4 - 120 VAC neutral wire to IRI gas valve - N/A on VF boilers.

J15 Socket Not used on VF boilers
J1 Socket (MCB power supply from PDB)

• Pin 1 - 120 VAC hot wire
• Pin 2 - 120 VAC neutral wire
• Pin 3 - Ground

J18 Socket (Silicon Carbide igniter power)

• Pin 1 - Igniter 120 VAC hot wire
• Pin 2 - Igniter 120 VAC neutral wire

F2 Fuse - N/A on VF boilers - if fuse is removed or blown it will not effect operation of VF boiler
JP4 Jumper - Should be on - removed during manufacturing only
J16 Flame - Flame sensor connection (single wire connect on MCB - split wire serves two flame sensors)
JP2 Jumper - Set jumper on pins 1 & 2 for 2.7 amp igniter
JP3 Jumper - Should be on - removed during manufacturing only

C

J2 Pump / IRI Gas

J1 Line Pwr J18 SiCar

J15 Not Used

4

3

2

1

4

3

2

1

3

2

1

2

1

3
2
1

F2 Fuse

not used on

VF boilers

J16 Flame

JP2

JP3

JP4

The MCB circuit board is mounted upside down on VF boilers compared to the illustrations below.