VF BOILER SERVICE MANUAL
AOS WPC - Tech Training
22 of 72
Ashland City, TN © 2007
Servicing should only be performed by a Qualified Service Agent
POOR COMBUSTION - IGNITION PROBLEMS (CONT)
VFD Operating Parameters
Approximate MCB/VFD operating parameters for natural gas models are shown in the first
table below. Parameters for propane models are shown in the second table.
When combustion is poor, the firing rate of the boiler or blower speed is in question, or the
boiler is experiencing rough starts or ignition failure compare the values given here to actual
readings taken during the various operating states shown. Actual readings will vary
somewhat but should be relatively close to what is shown here when the MCB and the VFD
are operating properly.
Approximate Values Natural Gas
Blower Speed Control VFD
VW/VB
500
VW/VB
750
VW/VB
1000
MCB Instruction Pre/Post Purge Mode Approx - VDC
8.6
8.6
8.9
MCB Instruction Ignitor Warm Up Period Approx - VDC
3.7
3.7
3.7
MCB Instruction Min Mode 25% Approx - VDC
1.3
2.1
2.1
MCB Instruction Max Mode 100% Approx - VDC
4.3
7.2
7.7
Blower Speed Pre/Post Purge Mode - Approx RPM
5000
5000
5000
Blower Speed Ignitor Warm Up Period - Approx RPM
2200
2200
2200
Blower Speed Min Mode 25% - Approx RPM
800
1200
1250
Blower Speed Max Mode 100% - Approx RPM
2500
4100
4500
Blower Power Freq Pre/Post Purge Mode - Approx Hz
172 Hz
172 Hz
179 Hz
Blower Power Frequency Ignitor Warm Up Period - Approx Hz
75 Hz
75 Hz
75 Hz
Blower Power Frequency Min Mode 25% - Approx Hz
26 Hz
41 Hz
43 Hz
Blower Power Frequency Max Mode 100% - Approx Hz
85 Hz
144 Hz
155 Hz
Approximate Values Propane Gas
Blower Speed Control VFD
VW/VB
500
VW/VB
750
VW/VB
1000
MCB Instruction Pre/Post Purge Mode Approx - VDC
8.6
8.6
8.9
MCB Instruction Ignitor Warm Up Period Approx - VDC
3.7
3.7
3.7
MCB Instruction Min Mode 25% Approx - VDC
1.4
2.1
2.4
MCB Instruction Max Mode 100% Approx - VDC
4.3
7.7
7.7
Blower Speed Pre/Post Purge Mode - Approx RPM
5000
5000
5000
Blower Speed Ignitor Warm Up Period - Approx RPM
2200
2200
2200
Blower Speed Min Mode 25% - Approx RPM
1000
1300
1400
Blower Speed Max Mode 100% - Approx RPM
2500
4500
4500
Blower Power Freq Pre/Post Purge Mode - Approx Hz
172 Hz
171 Hz
179 Hz
Blower Power Frequency Ignitor Warm Up Period - Approx Hz
74 Hz
75 Hz
75 Hz
Blower Power Frequency Min Mode 25% - Approx Hz
27 Hz
43 Hz
47 Hz
Blower Power Frequency Max Mode 100% - Approx Hz
85 Hz
155 Hz
155 Hz