VF BOILER SERVICE MANUAL

AOS WPC - Tech Training

22 of 72

Ashland City, TN © 2007

Servicing should only be performed by a Qualified Service Agent

POOR COMBUSTION - IGNITION PROBLEMS (CONT)

VFD Operating Parameters

Approximate MCB/VFD operating parameters for natural gas models are shown in the first
table below. Parameters for propane models are shown in the second table.
When combustion is poor, the firing rate of the boiler or blower speed is in question, or the
boiler is experiencing rough starts or ignition failure compare the values given here to actual
readings taken during the various operating states shown. Actual readings will vary
somewhat but should be relatively close to what is shown here when the MCB and the VFD
are operating properly.

Approximate Values Natural Gas

Blower Speed Control VFD

VW/VB

500

VW/VB

750

VW/VB

1000

MCB Instruction Pre/Post Purge Mode Approx - VDC

8.6

8.6

8.9

MCB Instruction Ignitor Warm Up Period Approx - VDC

3.7

3.7

3.7

MCB Instruction Min Mode 25% Approx - VDC

1.3

2.1

2.1

MCB Instruction Max Mode 100% Approx - VDC

4.3

7.2

7.7

Blower Speed Pre/Post Purge Mode - Approx RPM

5000

5000

5000

Blower Speed Ignitor Warm Up Period - Approx RPM

2200

2200

2200

Blower Speed Min Mode 25% - Approx RPM

800

1200

1250

Blower Speed Max Mode 100% - Approx RPM

2500

4100

4500

Blower Power Freq Pre/Post Purge Mode - Approx Hz

172 Hz

172 Hz

179 Hz

Blower Power Frequency Ignitor Warm Up Period - Approx Hz

75 Hz

75 Hz

75 Hz

Blower Power Frequency Min Mode 25% - Approx Hz

26 Hz

41 Hz

43 Hz

Blower Power Frequency Max Mode 100% - Approx Hz

85 Hz

144 Hz

155 Hz

Approximate Values Propane Gas

Blower Speed Control VFD

VW/VB

500

VW/VB

750

VW/VB

1000

MCB Instruction Pre/Post Purge Mode Approx - VDC

8.6

8.6

8.9

MCB Instruction Ignitor Warm Up Period Approx - VDC

3.7

3.7

3.7

MCB Instruction Min Mode 25% Approx - VDC

1.4

2.1

2.4

MCB Instruction Max Mode 100% Approx - VDC

4.3

7.7

7.7

Blower Speed Pre/Post Purge Mode - Approx RPM

5000

5000

5000

Blower Speed Ignitor Warm Up Period - Approx RPM

2200

2200

2200

Blower Speed Min Mode 25% - Approx RPM

1000

1300

1400

Blower Speed Max Mode 100% - Approx RPM

2500

4500

4500

Blower Power Freq Pre/Post Purge Mode - Approx Hz

172 Hz

171 Hz

179 Hz

Blower Power Frequency Ignitor Warm Up Period - Approx Hz

74 Hz

75 Hz

75 Hz

Blower Power Frequency Min Mode 25% - Approx Hz

27 Hz

43 Hz

47 Hz

Blower Power Frequency Max Mode 100% - Approx Hz

85 Hz

155 Hz

155 Hz