beautypg.com

For further information contact ups direct ltd – APC 208 Vac User Manual

Page 19

background image

For further information contact UPS Direct Ltd:

Tel: 08456 445 002 - Fax: 08456 445 003 - Email: [email protected] - Website: www.upsdirect.com

Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual

15

The Overload LED is illuminated and the UPS emits a sustained alarm tone

The UPS is overloaded.

The connected equipment exceeds the specified “maximum load” as defined

in Specifications on the APC Web site, www.apc.com.
The alarm remains on until the overload is removed. Disconnect nonessential

equipment from the UPS to eliminate the overload condition.
The UPS continues to supply power as long as it is online and the circuit

breaker does not trip; the UPS will not provide power from batteries in the

event of a utility voltage interruption.

The Replace Battery/Battery Disconnected LED is illuminated

The Replace Battery/Battery

Disconnected LED flashes and a short

beep is emitted every two seconds to

indicate the battery is disconnected.

Check that the battery connectors are fully engaged.

Weak battery

Allow the battery to recharge for 24 hours and perform a self-test. If the

problem persists after recharging, replace the battery.

Failure of a battery self-test: Replace

Battery/Battery Disconnected LED

illuminates and the UPS emits short

beeps for one minute. The UPS repeats

the alarm every five hours.

Allow the battery to recharge for 24 hours. Perform the self-test procedure to

confirm the replace battery condition. The alarm stops and the LED clears if

the battery passes the self-test.
If the battery fails again, it must be replaced. The connected equipment is

unaffected.

The input circuit breaker trips

The connected equipment exceeds the

specified “maximum load” as defined

in Specifications on the APC Web site,

www.apc.com.

Unplug all nonessential equipment from the UPS.
Reset the circuit breaker.

The AVR Boost or AVR Trim LEDs are illuminated

The system is experiencing very high or

low utility voltage.

Have a qualified service personnel check your facility for electrical

problems. If the problem persists, contact the utility company for further

assistance.

Problem and/or Possible Cause

Solution