Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual
Configuration
UPS settings
Settings are adjusted through PowerChute software or optional SmartSlot accessory cards.
Function
Factory
Default
User Selectable
Choices
Description
Automatic
Self-Test
On startup and
every 14 days
(336 hours)
there after
• On startup and every
7 days (168 hours)
there after
• On startup and every
14 days (336 hours)
there after
• On startup only
• No self-test
Set the interval at which the UPS will execute a
self-test.
UPS ID
UPS_IDEN
Up to eight characters
(alphanumeric)
Uniquely identify the UPS, (i.e. server name or
location) for network management purposes.
Date of Last
Battery
Replacement
Manufacture
Date
mm/dd/yy
Reset this date when you replace the battery
module.
Minimum Capacity
Before Return from
Shutdown
0 percent
• 0%
• 15%
• 30%
• 45%
• 60%
• 75%
• 90%
Specify the percentage to which batteries will
be charged following a low battery shutdown
before powering connected equipment.
Voltage Sensitivity
The UPS detects
and reacts to line
voltage distortions
by transferring to
battery operation to
protect the
connected
equipment.
High sensitivity
Brightly
illuminated: high
sensitivity
Dimly illuminated:
medium sensitivity
No illumination:
low sensitivity
Adjust by pressing the VOLTAGE SENSITIVIY
switch (rear panel). Use a pointed object, (such
as a pen) to do so.
Note: In situations of poor power quality, the
UPS may frequently transfer to battery
operation. If the connected equipment can
operate normally under such conditions, reduce
the sensitivity setting to conserve battery
capacity and service life.
Alarm Delay
Control
Enable
• Enable
• Mute
• Disable
Mute ongoing alarms or disable all alarms.
Shutdown Delay
90 seconds
• 0 s
• 90 s
• 180 s
• 270 s
• 360 s
• 450 s
• 540 s
• 630 s
Set the interval between the time when the UPS
receives a shutdown command and actual
shutdown.