For further information contact ups direct ltd – APC 208 Vac User Manual
Page 15
For further information contact UPS Direct Ltd:
Tel: 08456 445 002 - Fax: 08456 445 003 - Email: [email protected] - Website: www.upsdirect.com
Smart-UPS 5000 VA 208/230 Vac Tower/Rack-Mount 5U User Manual
11
Indicator
LED
Indicator Title
Description
Diagnostic
Utility Voltage
The UPS has a diagnostic feature that indicates the utility voltage.
The UPS starts a self-test as part of this procedure. The self-test does not affect the
voltage display.
Press and hold the
button to view the utility voltage bar graph indicator. As
soon as the on-line LED starts flashing indicating a self-test is in progress, the five-
LED Battery Charge indicator will show the utility input voltage.
Refer to the figure on the left for the voltage reading.
Values are not listed on the UPS.
The indicator on the UPS shows the voltage is between the displayed value on the
list and the next higher value, (see Troubleshooting).
Feature
Button
Feature Title
Function
Power On
Press this button to turn on the UPS. Continue reading for additional
capabilities.
Self-Test
Automatic: The UPS performs a self-test automatically when tuned on, and
every two weeks thereafter (by default). During the self-test, the UPS
briefly operates the connected equipment on battery.
Manual: Press and hold the
button
for a few seconds to initiate the
self-test.
Cold Start
When there is no utility power and the UPS is off, the cold start feature will
switch the UPS and connected equipment onto battery power,
(see Troubleshooting).
Power Off
Press this button to turn off the UPS.
230 V 208 V
Battery
Charge