beautypg.com

American Power Conversion 240-320kW 480V User Manual

Page 7

background image

Stop/Start UPS and Operating the External Service Bypass

990-4039

User Guide APC Silcon 240-320kW 480V UPS

7

The UPS is now isolated. Maintenance/repair, disconnection or removal can now be carried out.

2.4

Start UPS (from complete power down)

2.4.1 UPS Start-up

CAUTION!

Recharge batteries out of service every 3 months to prevent damage.

WARNING!

Internal DC capacitor may contain energy even after the UPS has been switched off. Allow for
automatic discharge by waiting at least 5 minutes after switching off UPS and battery breakers
before working on the UPS.

CAUTION!

Make sure all cable connections are in place prior to first start-up.

NOTICE!

After first system start-up, check that battery temperature is displayable (press

and

simultaneously on the display – it reads NV (not valid) if incorrectly installed). A battery capacity
test is recommended after the electric installation.

NOTICE!

If for any reason the start-up procedure is interrupted, wait for the display to show the step 4
message: “Stop charge DC capacitors : YES” and repeat procedure from there.

Green / ON

Red / OFF

CAUTION!

Do not close the MCCBs in the Battery Breaker Box unless the display reads: “Close MCCB” -
otherwise the UPS may be damaged. If the display reads “DC capacitor charge error”, do not
close MCCB.
Call for assistance.