ELECTRIC COMBITHERM
—
INSTALLATION MANUAL
#MN-28677
PG
. 24
®
C O M B I T HE R M
WAT E R S U P P LY & I N S TA L L AT I O N R E Q U I R E M E N T S
WAT E R D R A I N A G E
The oven must discharge through an indirect waste pipe by means of an air gap. The drain fitting is
supplied with a 1-1/2-inch (41mm) NPT thread on one end and a 1-1/2-inch (41mm) barbed connection
on the opposite end.
A union is required. Install a 1-1/2-inch
(41mm) diameter connection, drain line and
clamp into place. The drain line must always be
a positive gradient away from the Combitherm
oven and not more than 12-inches (305mm)
before an air gap.
NOTE:
In the U.S.A., this equipment is to be
installed to comply with the Basic
Plumbing Code of the Building
Officials and Code Administrators
International, Inc. [BOCA], and the
Food Service Sanitation Manual of the
Food & Drug Administration [FDA].
If several units are to be connected to one drain
pipe, the dimensions of the pipe must be
sufficient to allow an unobstructed water drain
system.
1-1/4" (32mm) diameter NPT
WASTE PIPE
1-1/2" to 2" minimum diameter
(c. 38mm to 51mm)
2" (51mm)
Air Gap
AVERAGE
DRAIN WATER
TEMPERATURE
149°F (65°C)
1-1/2" (41mm)
diameter connection
required
1-1/2” (41mm)
diameter NPT
condensate pan
clean out