beautypg.com

Alto-Shaam 10.18 User Manual

Page 21

background image

ELECTRIC COMBITHERM

INSTALLATION MANUAL

#MN-28677

PG

. 19

®

C O M B I T HE R M

E L E C T R I C A L & I N S TA L L AT I O N R E Q U I R E M E N T S

An electrical wiring diagram is located behind the

control panel on the left side of the oven. The oven

must be installed by a qualified electrician. This

appliance must be branch circuit protected with

proper ampacities, in accordance with the wiring

diagram located in the electrical compartment of the

oven. The oven must be properly grounded in

accordance with the National Electrical Code and

applicable local codes.

Wire size for the main incoming power to the unit

must match the minimum size listed in the

specifications applicable to the specific oven model.

For supply connections, locate the wire size posted

on the label located on the electrical control box

cover, behind the service panel.

When connecting to a Delta-B (wild leg) on a 3-phase

system, the wild leg must be connected to line 3.

Before operating the oven, check all cable

connections in the electrical connection area for

tightness since connections can loosen during

transport.

NOTE: After both water and electrical connections

have been completed, operate the oven in
any cooking mode for a period of 15
minutes and recheck the main power
connections at the terminal block to make
certain they remain tight.

380-415V:

To prevent an electrical shock hazard between the

appliance and other appliances or metal parts in

close vicinity, an equalization-bonding stud is

provided.

An equalization bonding lead must be connected

to this stud and the other appliances / metal parts

to provide sufficient protection against potential

difference. The terminal is marked with

the following symbol.

FOLLOWING ELECTRICAL CONNECTION,
THE FAN M U S T
ROTATE IN THE SAME
DIRECTION AS THE ARROW LOCATED
ON THE OVEN FAN MOTOR.

T H I S A P P L I A N C E W I L L N OT F U N C T I O N
P RO P E R LY A N D DA M AG E C A N O C C U R I F
T H E M OTO R ROTAT I O N I S N OT C O R R E C T.

TO CHANGE MOTOR DIRECTION,

EXCHANGE TWO OF THE INCOMING PHASES

.

D A N G E R

ELECTRICAL CONNECTIONS MUST

BE MADE BY A QUALIFIED SERVICE

TECHNICIAN IN ACCORDANCE WITH

APPLICABLE ELECTRICAL CODES.

D A N G E R

To avoid electrical shock, this
appliance MUST be adequately
grounded in accordance with local
electrical codes or, in the absence of
local codes, with the current edition
of the National Electrical Code
ANSI/NFPA No. 70. In Canada, all
electrical connections are to be
made in according with CSA C22.1,
Canadian Electrical Code Part 1 or
local codes.

D A N G E R

ENSURE POWER SOURCE

MATCHES VOLTAGE STAMPED

ON APPLIANCE NAMEPLATE.

MOTOR WITH

ROTATION

DIRECTION

ELECTRICAL

CONNECTION

ELECTRICAL PANEL

TERMINAL BLOCK

GROUND

This manual is related to the following products: