Wiring must be performed by a qualified electrician.
•
Adhere to all national and local electrical codes.
•
Install a utility circuit breaker for input wiring, (see tables below).
220/230/240 V M
ODELS
Input Connections
Output Connection (optional)
Single-Phase: Wire to L1, N, and
.
Three-Phase: Wire to L1, L2, L3, N, and
.
Wire to L1A, N1, and
.
System Wiring
Number
of
Phases
Voltage
Current
Full Load
(Nominal)
External Input
Circuit Breaker
(Typical)
Wire
Size
(Typical)
Input
1
220/230/240 V
40 A
50 A / 2-pole
10mm
2
Input
3+
Neutral
380/400/415 V
15 A / phase when
online
40 A on L1 in bypass
50 A / 4-pole
10mm
2
SURT8000
Output
1
220/230/240 V
40 A
(not required)
10mm
2
Input
1
220/230/240 V
50 A
63 A / 2-pole
16mm
2
Input
3+
Neutral
380/400/415 V
18 A / phase when
online
50 A on L1 in bypass
63 A / 4-pole
16mm
2
SURT10000
Output
1
220/230/240 V
50 A
(not required)
16mm
2