Trio Motion Technology MC4N-ECAT User Manual
Page 11
39mm
145mm
4mm
4mm
4mm
4mm
SHIELD SCREW
CHASSIS MOUNTING
DIMENSIONS
(LOOKING FROM
FRONT)
M4 screws should be used in
2 places to mount the MC4N
to to an unpainted metal
panel.
The best EMC performance
is obtained when the MC4N
is attached from the shield
screw (marked) using a fl at
braided conductor with
a cross section of 4mm x
1mm. Do NOT use a circular
section wire or run the braid
to a central star point.
Ensure that the ventilation
slots at the top and bottom
of the MC4N are kept clear
to ensure a free fl ow of air
through the module.