Start-up – Timeguard 201.0.090 User Manual
Page 7

4
4. Start-up
The detectors are supplied ready for operation with a factory setting of recom-
mended standard values.
The QuickSet plus service remote control for starting-up the system is opti-
onally available. With the remote control all potentiometer values can be set
from a distance.
4.1 Settings for switching contact A «Light»
Potentiometer
Brightness threshold “LUX”
Scale
Transfer zones (no working area)
approx. 2
Bright transfer zones
approx. 4
Deactivation of brightness measurement
“on”
Depending on the installation location,
natural light intensity, furniture, reflec-
tion characteristics of the room and the
furniture it may be necessary to correct
the settings by 1-2 steps on the scale.
For ease of setting up, we recommend
the service remote control QuickSet
plus.
●
●
●
GB
- TS800B (8 pages)
- TG64B (8 pages)
- ETU17 (12 pages)
- TG77 (12 pages)
- NTT01 (6 pages)
- NTT02 (6 pages)
- NTT03 (12 pages)
- NTT05 (6 pages)
- NTT06 (12 pages)
- NTT08 (12 pages)
- TGBT4 (6 pages)
- TGBT5 (6 pages)
- TGBT6 (6 pages)
- FST11A (12 pages)
- TS900B (6 pages)
- NTM01 (6 pages)
- NTM02 (12 pages)
- TR 671 top (12 pages)
- MEU11 (7 pages)
- EL11 (12 pages)
- PB05 (8 pages)
- EMU56 (12 pages)
- TR 608 top2 (24 pages)
- TR 611 top2 (14 pages)
- TR 612 top2 (7 pages)
- SELEKTA 170 top2 (24 pages)
- TR 641 top2 (36 pages)
- LUNA 109 (8 pages)
- LUNA 110 (8 pages)
- LUNA 112 top2 (14 pages)
- LUNA 120 top2 (14 pages)
- E169S (1 page)
- E269H (2 pages)
- ELU56 (2 pages)
- ELU5620 (2 pages)
- TR 635 top2 (16 pages)
- RTS113 (8 pages)
- ZV700 (12 pages)
- ZV210 (2 pages)
- ZV810 (14 pages)
- DS1 (16 pages)
- DS4 (2 pages)
- DS3HD (10 pages)
- RLS010 (2 pages)
- ECO36PIR (8 pages)