Technical data – Timeguard TR 636 top2 User Manual
Page 16
16
Technical data
• Operating voltage: 230 –240 V~, +10 %/-15 %
• Frequency:
50–60 Hz
• Power consumption: 0,8 W (TR 635 top2),
0,9 W (TR 636 top2)
• Standby:
0,9 W (TR 635 top2),
1,1 W (TR 636 top2)
• Switch output:
switching of choice of
external wires is permitted
• Contact:
two way switch
• Gap:
<3 mm (µ)
• Contact material: AgSnO
2
• Max switching capacity: TR 635 top2:
16 A, 250 V~, cos ϕ = 1
10 A, 250 V~, cos ϕ = 0,6
TR 636 top2:
6 A, 250 V~, cos ϕ = 1
6 A, 250 V~, cos ϕ = 0,6
• Min. switching capacity: 10 mA/230 V AC
100 mA/12 V AC/DC
• Incandescent lamp load + Halogen lamp load:
2300 W (TR 635 top2)
1200 W (TR 636 top2)
• Fluorescent lamp load: uncorrected +
(VVG)
series corrected 1000 VA
parallel correction 400 VA (42µF)
• Compact fluorescent lamps: 90 W
• LED lamps:
<2 W output, max. connec-
tion total of 20 W,
>2 W < 8 W output, max.
connection total of 50 W
• Permissible ambient temperature: –30 °C ... +55 °C
• Protection class: II in accordance with
EN 60730-1 subject to
designated installation
• Protection rating: IP 20 in accordance with
EN 60529
• Time accuracy:
≤ ±0,5 s/day at +20 °C
• Power reserve:
10 years (lithium call) at +25 °C
• Pollution degree:
2
• Rated impulse withstand voltage: 4 kV
• TR 635 top2:
max. switching cycles with
16 A resistive load: 50,000
• TR 636 top2:
max. switching cycles with
6 A resistive load: 50,000