beautypg.com

Function, Self-diagnostics, Functional test of co – ROTRONIC CF8-W-Disp-AL User Manual

Page 4: Sensor cf8-w-disp-al

background image

Dokument
UMA 145

Rev
3

Page
4 (8)

Jumper

Positio

n

Function

Start

point

selection

jumper

0%

20%


Jumper top position provides 0Vdc or 0mA start point for Out(1),
Out(2)
(0-20mA or 0-10V).

Jumper bottom position provides 2Vdc or 4mA start point for Out(1),
Out(2) (4-20mA or 2-10V).

Communi

-cation

selection

jumper

MB

SA


Jumper at top position provides Modbus communication protocol

Jumper at bottom position SenseAir communication protocol


Out(1)

Current

Voltage


Connection in position “Current” provides 0/4-20mA output range for
Out(1).

Connection in position “Voltage” provides 0/2-10VDC output range for
Out(1).


Out(2)

Current

Voltage


Connection in position “Current” provides 0/4-20mA output range for
Out(2).

Connection in position “Voltage” provides 0/2-10VDC output range for
Out(2).

Table II. Configuration jumpers for CF8-W-Disp-AL


FUNCTIONAL TEST of CO

2

Sensor

CF8-W-Disp-AL


The unit has three LED’s – one yellow and two red – to indicate the status of the
controller.

Yellow LED - ”Call for maintenance” is lit, if an error flag is set or the measurement is
out of range. This information is also shown on the display by the wrench icon.

Left red LED - ”the relay1 is actuated” is lit, when Out(3) (relay1) is actuated (closed).

Right red LED
- ”the relay2 is actuated” is lit, when Out(4) (relay2) is actuated
(closed).

A simple and visual functional test can easily be performed. Take a breath and blow
the air from a distance of a few centimetres on the sensor. The sensor will detect a
rapid increase in the carbon dioxide concentration. The red LEDs are lit when the
CO

2

concentration passes the pre-set values.

Self-diagnostics


The system contains complete self-diagnostic procedures. A full system test is
executed automatically every time the power is turned on. In addition, constantly