beautypg.com

Default output range, Formulas for calculation of output values, Output configurations – ROTRONIC CF8-W-Disp-AL User Manual

Page 3

background image

Dokument
UMA 145

Rev
3

Page
3 (8)

Terminal

Default

Output

Default Output

Range

Outputs of this

sensor

Output Range of this

sensor

OUT1

0-20 mA

0-4 % CO

2

OUT2

4-20 mA

0-4 % CO

2

Relay 1

Closed

Open

> 1,5 % CO

2

< 1,4 % CO

2

Relay 2

Closed

Open

> 3,0 % CO

2

< 2,9 % CO

2

Table I. Default output configurations for CF8-W-Disp-AL

Formulas for calculation of output values


Configuration


Output Range


Formula for calculation


0-10 VDC


0-4 % CO

2


CO

2

value = Volt/10*4


2-10 VDC


0-4 % CO

2


CO

2

value = (Volt –2)/8*4


4-20 mA


0-4 % CO

2


CO

2

value = (mA-4)*4/16


a-b


c–d


Value = (reading-a)/(b-a)*(d-c)+c

a = lowest value of the configuration
b = highest value of the configuration
c = lowest value of the range
d = highest value of the range

Table II. Calculation of CO

2

value for CF8-W-Disp-AL



Output Configurations


If other options are needed for the application, the output jumpers have to be
configured before the unit is powered up. Each jumper selection is independent from
the others, except for the “Start point selection” jumper, which affects both, Out(1) &
Out(2), linear outputs. Alternative measuring ranges of the outputs can be selected
with the software UIP (version 4.3 or later).