Ds−2c, Setting the configuration switches and adjustments – Ouellet DS-2C User Manual
Page 6
NEUTRAL BUS BAR
C
B1
BROWN
BLUE
YELLOW
YELLOW
LOAD
LOAD CENTER
C
B2
DS−2C
POWER SUPPLY
120VAC In, 240VAC Load, Separate Feed
CB
BROWN
BLUE
YELLOW
YELLOW
LOAD
LOAD CENTER
DS−2C
POWER SUPPLY
240VAC In, Dry Contact for Boiler/Circulation Pump
These are just some of the possible wiring schemes that can be used to connect the DS-2C to your load for
control. Remember, these are only suggestions. You should always consult a qualified
electrician or inspector to assure conformance with applicable local and national
electrical codes!
6
Setting the Configuration Switches and Adjustments
The following paragraphs and table outline the operating modes for the DS-2C and
explain the functions of the adjustments. Trigger temp (TT) is adjustable from
34°F-44°F (1°C-6°C) using the TRIG TEMP control. When ambient air
temperature (AT) is below this setting precipitation is assumed to be snow. When
above this setting, precipitation is assumed to be rain.
The DEL configuration switch activates the Delay-Off drying cycle timer on the DS-
2C. The timer allows the DS-2C to continue to operate and dry the heated surface through evaporation
once precipitation has stopped. The drying cycle reduces the chance of
moisture left behind refreezing into ice. This timer is restarted by each
sensor trigger. Therefore, the DS-2C will continue to operate as long as it is
triggered, then for the Delay-Off period once the trigger clears. All "sensor"
modes (DEL off) provide a 2 minute Delay-Off time. When in "controller"
mode (DEL on) the Long Delay (LD) configuration switch determines the time
span of the drying cycle. The Delay-Off time can be adjusted from 30-90
minutes (LD Off) or 2-6 hours (LD On) using the DELAY OFF control.
The Low Temperature Cutoff (LTC) option is typically used on snow melting
systems with limited output capacity where melting cannot be maintained at
very low temperature. If selected, the snow sensor will clear a trigger below
5°F (-15°C) even if snow is still falling. It will resume normal operation
above 9°F (-13°C). However, the sensor will remember if it was triggered
before the drop below 5°F or if snow was detected during the cold period. If
so, the sensor will execute one Delay-Off cycle when the temperature rises
above 9°F in order to melt any snow left behind during the cold period. This
is referred to as RECOVER mode. Care should be exercised in using this mode as the potential
exists for ice to be formed on the melting surface.
The DS-2C precipitation sensor is very sensitive and can detect a single snow flake or rain drop. However,
if the DS-2C is mounted in an area susceptible to high winds, overhanging trees, or blowing ground snow,
nuisance triggering may occur. While proper placement is the best remedy, the SENSITIVITY control can
also be used to reduce nuisance triggering. An internal timer checks the precipitation sensor for moisture
and compares cleared time with triggered time. The highest sensitivity
setting (toward MORE) triggers on first detection. As the control is
adjusted clockwise precipitation must be detected for a longer period to be
considered valid. The lowest sensitivity setting (toward LESS) requires
120 seconds of detection before the unit triggers. If a trace amount of
snow blows onto the grid from a drift or overhang it will likely be melted
and evaporated in less than a minute. Similarly, a very light snowfall may also clear quickly from the grid.
If these conditions should be ignored by the sensor the SENSITIVITY control can be adjusted as required.
However, to prevent non-triggering during a true event, it is recommended that the user start at highest
sensitivity (MORE), then adjust while monitoring operation over time.
THE UNIT MUST BE IN STANDBY/RESET TO CHANGE CONFIGURATION SWITCHES
L'appareil doit être en mode STANDBY/RESET pour modifier commutateurs de configuration
3