NORD Drivesystems TI 276997120 User Manual
Technical information / datasheet, Notice, Validity of this document
Technical Information / Datasheet
Link circuit choke
SK DCL-950/120-C
1.0
Erstausgabe / first issue
1014
Rck
TI 276997120
GB
version
reason for change(s)
issue
name
document
speech
Pos : 1 /T ec hnis che Inf or mationen/Dr oss eln/SK DC L-950/120-C / 276997120 / Basisi nf or mationen [SK DC L-950/120-C] @ 4\ mod_1388745773880_388.doc x @ 110002 @ 5555 @ 1
SK DCL-950/120-C
Part number: 276 997 120
Link circuit choke
NOTICE
Validity of this document
This document is only valid in combination with the operating instructions of the relevant frequency inverter and
under strict compliance with the safety and warning instructions which they contain. All of the information that is
relevant for a safe start-up of this module and the frequency inverter is only available under these conditions.
Scope of delivery
1 x
Module
SK DCL-950/120-C
1 x
Enclosed package for
creating protection
against contact (not
IP20)
Shrink tube
Usage area
Link circuit choke to improve mains quality. Due to its principle of operation, distortions of the mains
voltage caused by the frequency inverter are considerably reduced by the use of a link circuit choke.
The harmonic component of the current is reduced to approx. 40% and the power factor (lambda) is
increased. The module is installed in the immediate vicinity of the frequency inverter.
Frequency inverter assignment
Permissible frequency inverters (FI)
FI size
FI power
SK 5xxE-452-340-A
…
SK 5xxE-552-340-A
8
45 kW / 55 kW
Technical data
General
Temperature range
-10 … 50°C
Temperature class
F (VDE) / Class 155 (UL)
Protection class
IP00
Fastening
4 x M6
Weight
12.5 kg