eServer Setup and Site Installation Instructions
© Mass Electronics Pty Ltd 2009
Chapter 2 – Installation and Configuration
2-2.2.2 Port Forwarding and Firewalls
The following Ports are required to be opened through the Firewall to allow incoming and outgoing
connections to specific parts of the Innotech System.
NOTE
At a minimum ensure to enable Port 80 (Internet), Port 1433 (SQL database), Port 20000 (iComm) and Port 20001
(eServer graphics).
1
Enabling VNC, FTP or VPN assists with remote site access to the computer for management and
file transfers. This is optional but highly recommended as it allows remote diagnostics, analysis
and troubleshooting of site problems if they occur.
2
Enabling Ports 8227, 8228 and 8230 is only necessary for remote access using Chronicle Manager
to configure the site Chronicle Server.
3
The HASP security dongles used by eServer and Magellan do not fully support Remote Desktop.
You will not be able to launch eServer or Magellan through Remote Desktop.
Required Ports
Usage
Port 80
Standard Internet Port
Port 20000
Innotech Communications Server (iComm)
Port 20001
Innotech eServer Graphics
Port 21000
Innotech Facility Manager (if required)
Port 1433 (TCP)
SQL Server Express database
Recommended Additional Ports
1
Port 5900
For VNC (Virtual Network Computing)
Port 21
For FTP (File Transfer Protocol)
Port 1723
For VPN (Virtual Private Network)
Optional Ports
Usage
Port 8227, 8228, 8230
2
Innotech Chronicle Manager remote communications with the
Chronicle Server (if required)
Port 3389
3
For Remote Desktop (mstsc)
Table 2-1:
Required Ports for an Innotech System