beautypg.com

Dwyer BGM User Manual

Page 2

background image

FRONT PANEL CONTROLS

PEAK / ^ (SET)
• Press and hold to view peak value
• To reset the peak value - while holding ‘PEAK’, press ‘SETPT/RESET’
momentarily.
• When in the setpoint or menu mode, this button changes the setting for
a parameter or increments the flashing digit.

SETPT / RESET
• Press momentarily to view/set setpoint 1 - see instructions below to set
a setpoint or scaling value.
• Press again momentarily to view/set setpoint 2 - see instructions below
to set a setpoint or scaling value.
• Press again momentarily to return to the operate mode.
• Press while holding ‘PEAK’, ‘VALLEY’ or ‘TARE’ to reset those values.

TARE
• Press momentarily to zero meter display.
• Display offset (TARE) value is stored until power is removed, menu is
entered or TARE is reset.
• To reset the TARE value - while holding ‘TARE’, press ‘SETPT/RESET’
momentarily.

MENU
• Press to enter the menu/scaling mode.
• Press again to exit the menu/scaling mode.

VALLEY / > (STEP)
• Press and hold to view valley value.
• To reset the valley value - while holding ‘VALLEY’, press
‘SETPT/RESET’ momentarily.
• When in the setpoint or menu mode, this button advances to the next
parameter or to the next digit.

CONNECTOR / PIN DESCRIPTIONS

P1 - SIGNAL INPUT
P1 - 1: SIGNAL INPUT
P1 - 2: SIGNAL RETURN
P1 - 3:+VOLTAGE RETRANSMISSION (OPTIONAL)
P1 - 4: -VOLTAGE RETRANSMISSION (OPTIONAL)

P2 - REMOTE CONTROL INPUTS
P2 - 1: GROUND RETURN
P2 - 2: TARE
P2 - 3: SETPT / RESET
P2 - 4: PEAK / ^ (SET)
P2 - 5: VALLEY / > (STEP)
P2 - 6: MENU

Above inputs are all active low - short input to ground return or pull to
logic low to activate function; see front panel control section for a
description of each function.

Installation of a shorting jumper between pins P2-5 and P2-6 disables
the five front panel push buttons.

P3 - SETPOINT RELAY OUTPUT
Note: This terminal block position will only be present if the meter is
equipped with the corresponding option.

Note: Setpoint relays are rated at 200 VAC/DC @ 1 AMP maximum.

P3 - 1: SETPOINT 1 RELAY
P3 - 2: SETPOINT 1 RELAY
P3 - 3: SETPOINT 2 RELAY
P3 - 4: SETPOINT 2 RELAY

P4 - POWER INPUT
See power supply specifications (page 1) for connection information.

4 WIRE TRANSDUCERS

ie: LOAD CELL VOLTAGE INPUT METERS

3 WIRE TRANSDUCERS

ie: LINEAR POT VOLTAGE INPUT METERS

TRANSCONDUCTANCE SENSORS

ie: PH PROBE CURRENT INPUT METERS

2 WIRE LOOP POWERED PROBES

ie: 4-20 mA TEMPERATURE TRANSMITTER

CURRENT INPUT METERS