beautypg.com

Specifications, Dimensions – Dwyer SC1290 User Manual

Page 7

background image

December,

2004

Page 7 of 8 949-0530

Rev. 2

SPECIFICATIONS

Power Supply:

SC1290:

85 to 265 VDC / VAC 50 to 400 Hz.

SCL1290:

12 to 24 Vdc/Vac 50 to 400 Hz. ±20%.

Isolation:

1500 V rms between outputs, input, and power.

Set Points: Adjustable 0 to 100% of span.
Deadband: Adjustable 0.25% to 100% of span.
Drift: ±0.02% / °C typical, ±0.05% / °C maximum.
Ambient Temperature Range:

Operating:

0° to 55° C (32° to 131° F)

Storage:

-40° to +80°C (-40° to +176°F)

Humidity Conditions: 0 to 90% up to 40 °C non-condensing, 10 to 50%
at 55 °C non-condensing.
Input impedance: 3 megohms.
Relay output: SPDT, one per set point, 5A @ 250 VAC, resistive.
Latch circuit reset: Automatic at power up. Manual with reset switch

on front of module.

Indicators: One dual color LED per set point. Red = relay on, green

= relay off.

Sensor Burnout Protection: Selectable, upscale or downscale.

DIMENSIONS

AL

DB

RESET

DIN EN 50022-35
(not supplied)

ADAPTER BRACKET
FOR SURFACE MOUNTING
(OPTIONAL)

KIT#: 1007-35DINADPTR

(1.40)

35.5

(0.886)

22.5

(2.950)

75

(3.880)

7

10

8

11

9

12

B

A

All dimensions in
millimeters (inches)