Parameter Description
Compressor / Set Point Menu

SEt

Sets the Ambient Temperature set point between r1 and r2

r0

Differential or hysteresis for set point
(For d0 = re)
Ambient temperature ≥ SEt + r0

Output On

Ambient temperature ≤ SEt

Output Off

(For d0 = in)
Ambient temperature ≤ SEt - r0

Output On

Ambient temperature ≥ SEt

Output Off

r1

Minimum value for set point

r2

Maximum value for set point

c0

Minimum time compressor must remain off before being
restarted

c1

Duration of cold cycle

c2

During probe error, time that output is engaged

c3

During probe error, time that output is disengaged

c4

Minimum time compressor must stay on

c5

Minimum time between compressors starts

Defrost Menu

d0

Selection for Heating or Cooling Operation
re = Cooling
in = Heating

d2

Maximum time the control will be in defrost cycle. If set to zero,
control will not defrost.

d3

Hour of the day for the first defrost. No defrost cycles will take
place before this time.

d4

Upon powering on the control, delay time before first defrost
cycle.

d5

Display during defrost cycle.
Off = Current temperature displayed.
On = Temperature at start of defrost cycle displayed until
defrost cycle ends and the temperature is less than or equal
to starting temperature or after the time is set in d6.

d6

Maximum time before the display returns to normal reading
after a defrost cycle.

d7

Time after defrost cycle before the compressor can be started.

d8

Time between defrost cycles. If set to 0, defrost must be
manually actuated.

d11

Minimum duration the control remains in defrost cycle.

d14 Units to count the defrost cycle

rt = according to the time the controller was on.
ct = according to the time the compressor was on.

HdE Hours until next defrost cycle.
ndE Minutes until next defrost cycle.

Display Menu

P0

Selection of Engineering Unit (F or C)

P1

Ambient Probe Calibration Adjustment

P4

Decimal Point Present

Alarm Menu

A0

Alarm Differential or hysteresis

A1

High Alarm Set Point (Deviation Value)
On when temperature reaches Set + A1 and off at Set +
A1 - A0

A2

Low Alarm Set Point (Deviation Value)

A3

Time of Alarm Inhibit after Continuous Cool Cycle

A4

Time of Alarm Inhibit after Defrost Cycle

A6

Time of Alarm Inhibit after Power Up

A7

Time since Alarm Initiated until Validated

Initial Setup Menu

Hor

Real Time Hours

nin

Real Time Minutes

H0

Restore Factory Configuration

H2

Keypad Password Protected
Yes = code is necessary to start/stop defrost or continuous
cold cycle. One minute after entering the code, keypad is
locked again
No = Keypad not protected

H3

Compressor delay time upon power up

H4

Address for serial communications (Need Model TS485
communication module)

H5

Input code to Parameters (factory set at 0)

H6

Input Probe Types: PTC or NTC

H11 HACCP Alarm recording enabled or disabled

dAt

Real Time Date can be programmed by holding the set key for
3 seconds. Then, use arrows to select day. Press set to store
day; use arrows to access month and year

td

The display refreshes at 1 degree if actual temperature is
greater than 1 degree higher td seconds before during defrost
and open door conditions

Front Panel Operation

Set Point Setup

• Press the Set key once and Set will be displayed.
• Press Set key again and set point value will be shown.
• Uses the Up and Down arrows to adjust set point.
• Press the Set key to save the new set point.
• Press Set and Down arrow at same time to exit.

Time Setup

• Press the Set Key once and Set will be displayed.
• Use the Up and Down arrow until Hor is displayed for adjusting the

hours.

• Press the Set key to view the current value.
• Use the Up and Down arrow to adjust to current time.
• Press the Set key for 8 seconds to save the new time (Pro will flash

on display once the value is saved).

• Press the Set key to return to the previous menu.
• Use the Up and Down arrow until Nin is displayed for adjusting the

minutes.

• Repeat steps 3 through 6.
• Press the Set and Down arrow at the same time to exit.

Parameter Programming
The parameters are organized into 6 programming menus (COn, dEF,
PrO, ALA, HAC, and Ini) (HAC is only accessible when H11 = yes).

• Press the Set key for 8 seconds until 0 is displayed.
• Use the Up and Down arrows to reach the assigned security code

(factory setting for this code is 0).

• Press the Set key to accept the code.
• Use the Up and Down Arrows to select programming menu to

enter.

• Press the Set key to reach the parameters under each

programming menu.

• Use the Up and Down Arrows to scroll through the parameters.
• Press the Set key to view the value of the parameters.
• Use the Up and Down Arrows to change the values of the

parameters.

• Press the Set key to save the changes.
• Press the Set and Down Arrow to go back to the programming

menu selection.

• Press the Set and Down Arrow a second time to exit.