WARNING:
A voltage potential between the ground wire of the unit and the ground
of other equipment can lead to electrolytic corrosion. Always ensure the
grounding system provides an equipotential between the transmitter and
the earthing ground connection. Avoid using the power system protective
ground since this will often have a significant potential difference to the
transmitter ground. Also note that dissimiliar metals in the ground system
may cause electrolysis corrosion of the transmitter or other components
in the ground system.
During installation, connect a voltmeter or ammeter between the shield
ground wire and the grounding connection. If there is a measurable volt-
age or current electrolytic corrosion may be a serious possibility. If there
is a potential difference then some isolation system will be required.
Improper grounding may lead to damage or poor signal integrity.
MAINTENANCE/REPAIR
Upon final installation of the Series MBLT, no routine maintenance is
required. The Series MBLT is not field serviceable and should be
returned if repair is needed (field repair should not be attempted and may
void warranty).
WARRANTY/RETURN
Refer to “Terms and Conditions of Sales” in our catalog and on our web-
site. Contact customer service to receive a Return Goods Authorization
number before shipping the product back for repair. Be sure to include a
brief description of the problem plus any additional application notes.
©Copyright 2013 Dwyer Instruments, Inc.
Printed in U.S.A. 12/13
FR# M2-443891-00 Rev. 2
MERCOID DIVISION
DWYER INSTRUMENTS, INC.
P.O. BOX 258 • MICHIGAN CITY, IN 46361 U.S.A.
Phone: 219/879-8000
www.dwyer-inst.com
Fax: 219/872-9057
e-mail: [email protected]
Example
Construction
Circuit
Options
Body
Material
Accuracy
Output
Reference
Cable
Material
Range Unit
Range Value
Cable
Length
Options
MBLT
MBLT
2
2
S
S
MBLT-2SC-IVPF-30-50-NIST
Narrow bullet
Surge protected
316 SS
0.10%
0.25%
4 to 20 mA
Vented
Polyether polyurethane
ETFE
Feet of water column
Meter of water column
PSI
In feet for feet and psi range,
in meters for meter range
NIST Traceable Certificate
Model Number Guide
C
B
C
F
F
M
P
I
I
V
V
P
P
E
30
X
50
X
NIST
NIST