beautypg.com

Caleffi 524 User Manual

Page 9

background image

ENGLISH

This installation guide has been produced for the 524 series thermostatic

products. These instructions cover the installation, operation and

maintenance of the 524 series thermostatic mixing valves. Please read

the enclosed instructions before commencing the installation of this

product, please note;

The installation must be carried out strictly in accordance with the Water

Supply Regulations and any local authority regulation.

Temperature setting range :

30 ÷ 65 ° C

Temperature stability :

± 2 ° C

Max working pressure :

( static )

10 bar

( dynamic )

5 bar

Max inlet temperature :

90 ° C

Maximum inlet pressure ratio ( H/C or C/H ) :

2 : 1

Min. temperature differential to ensure fail safe
between hot and cold supplies :

10 ° C

INTRODUCTION

WE RECOMMEND THAT THE INSTALLATION OF ANY CALEFFI

PRODUCT IS CARRIED OUT BY AN APPROVED INSTALLER

TECHNICAL DATA

9