Blue-White CHEM-PRO C3 ProSeries Diaphragm Pump User Manual
Page 13

Page 12
Page 13
Flow verification sensor sold separately.
Flow verification system is designed to stop pump in an event sensor does not detect flow during pump operation.
Indicating an empty chemical tank, clogged injection fitting, loose tubing connection, etc.
To allow pump to clear any gasses that may have accumulated over time, an alarm delay time value from 1 to 255
seconds must be programmed.
Note: An alarm delay of 000 seconds disables FVS system.
Step 3
Press and release START | STOP button to scroll through
menu until you see FVS icon.
If you pass FVS screen, continue to press and release
START | STOP button until FVS icon appears.
Step 4
FVS icon will appear for 1 second, followed by numbers.
These numbers indicate delay time setting for FVS.
Select a delay time in seconds. Delay time is amount of time
pump will wait to receive a pulse from sensor until an alarm
is triggered.
A delay time of 00 deactivates FVS feature.
FVS
0
00
0
Step 5
After you’ve made your selection, press and release START
| STOP button. This saves your setting.
Press and hold START | STOP button to exit Setup menu
and return to runtime screen.
Flow Verification Sensor is designed to give you two installation options.
Sensor can be installed:
!
Directly onto pumphead of Chem-Pro® pump, discharge side.
!
Anywhere on discharge side of Chem-Pro® pump.
Wiring for sensor can be connected directly to a Chem-Pro® pump. Pump will stop pumping if sensor detects no
flow. A relay will then close allowing for remote alarm indication or initiation of a back-up pump.
Install FVS Flow
Sensor - Flow Verification Sensor should be installed on inlet (suction) side of pump tube.
When installing directly onto pump 3/8” tube discharge fitting:
Sensor includes a PVC tubing insert, located inside sensors female thread connection, that is designed to
seal sensor onto pump tube adapter. Thread sensor onto pump tube until tubing insert is snug against pump
tube fitting - do not over-tighten.
SEC
7.1
Set FVS (flow verification system)
7.1
Set FVS (flow verification system) - Continued
Time-out - Chem-Pro pumps have a time-out setting of 20 seconds while in configuration menus. If built-in timer exceeds 20 seconds
without a button being pressed, then pump will exit configuration menu. Changes will only be saved after RIGHT arrow button is
pressed and released.
Step 1
Press and release STOP button
Note: Cannot enter programming mode while pump is in running.
off
Step 2
Press and hold START | STOP button until ‘Remote’ icon
begins flashing.
This indicates that you’ve entered Setup menu.
no
0
Remote
Icon
REMOTE
off
Sensor Model Number
Actual Working Range with
Chem-Pro® Pump
ML/Min
ML/Min
30-200
FV-100
30-300
Published Flow Range
50-900
FV-200
100-1000
100-1800
FV-300
200-2000
300-3000
FV-400
300-3000
500-5000
FV-500
500-5000
700-7000
FV-600
700-7000
Confirm FVS flow range - Flow Verification Sensor (FVS) will only function within its operating range. See chart
for available ranges.
NOTE: If pump output is less than 30 ml/min, sensor will not detect chemical and a signal will not be sent to
pump, resulting in an alarm condition.
NOTE: For low viscosity (water-like) fluids only. Consult factory if attempting to use with viscous fluids.