3.4
PARAMETER SEQUENCE
PM090-3
Volume II
3-3
59135
Parameter
Description
(Primary
Display)
Parameter
Description
Adjustment Range
Input
Range
Selects the input sensor
type, resolution and
display scale (
°
C or
°
F)
by means of a code
number.
See Table 3-1.
Range
Trim High
Adjusts the maximum
range value of the input
type selected.
Range Trim Low (see below) to
Range Max. (see Table 3-1).
Range
Max.
Range
Trim Low
Adjusts the minimum
range value of the input
type selected.
Range Min. (See Table 3-1) to
Range Trim High (see above)
Range
Min.
Power
Supply
Frequency
Applicable to
DC-powered units only,
this must be set to the
mains (line) frequency
for the site in order to
ensure proper filtering of
the input signal.
50Hz
60Hz
60Hz
Alarm 1
Type
Defines the action of
Alarm 1
Process High
Process Low
No alarm
Process
High
Alarm 2
Type
Defines the action of
Alarm 2
Process High
Process Low
No alarm
No
alarm
Output 1
Usage
Determines how NPN
Output 1 and Relay 1
operate.
Alarm 1, non-
latching, direct
action
Alarm 1, non-
latching, reverse
action
Alarm 1, latching,
direct action
Alarm 1, latching,
reverse action
Logical OR Alarm
1 & 2, direct
action
Logical OR Alarm
1 & 2, reverse
action
Alarm 1
non-
latching
direct
action