PARAMETER SEQUENCE
The Program Mode parameter sequence is as follows:
2-3
Volume I
OM090-2
59135
Parameter
Description
(Primary
Display)
Parameter
Description
Adjustment Range
Re-
transmission
Scale
Minimum
The lower end of the linear
scale for the
re-transmission output,
expressed as the value
corresponding to the
minimum output signal.
−
19999 to 99999
−
19999
Re-
transmission
Scale
Maximum
The upper end of the
linear scale for the
re-transmission output,
expressed as the value
corresponding to the
maximum output signal.
−
19999 to 99999
99999
Process
Variable
Offset
Corrects a known offset of
the input in order to
display more accurately
the process value.
−
19999 to 99999
0.00
Input Filter
Time
Constant
Filters the input over a
user-definable time period
to minimise the effect on
the process variable of
any extraneous impulses
0.0 (OFF) to 100.0
2.0
Comm-
unications
Address
The unique serial
communications address
of the instrument.
1 to 99
1
Baud Rate
Serial communications
speed
1200, 2400, 4800 or 9600 4800
Display
Colour
Change
Defines the colour of the
primary and secondary
displays prior to/after the
preset value (e.g. Alarm
level) is reached.
Red
Green
Green
to Red
Red to
Green
Green to
Red
Alarm Lock Enables/disables the
changing of alarm values
via the front panel.
Enabled
Disabled
Enabled
Help Prompt Determines whether the
Primary Display shows the
parameter description for
3 seconds before a
parameter value is shown.
Yes
No
Yes