Spectrex 20/20R - Single IR Flame Detector User Manual
Page 61
Spectrex Inc. - SharpEye
TM
Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005
53
Specifications
Mechanical
Explosion Proof Enclosure:
NFPA (designed to meet)
Class I, Division 1 & 2 Groups B, C and D
Class II, Division 1 & 2 Groups E, F, and G
ATEX (designed to meet) EX II2G
EExd IIB T5 50˚C per En 50-014 & EN50-018
Electrical
Power: 8 VDC Max.
6 x Rechargeable 1.2 VDC NiCd Batteries
Current: 2.5A Avg.
Charge: 400mA for 14 Hours
Environmental
Temperature Range:
-4º F (-20º C) to 122º F (50º C)
Vibration Protection:
1g (10-50hz)
Water and Dust:
IP 67 per EN 60529
Physical
Dimension: 11.5 x 10.1 x 3.9 in (292 x 258 x 100 mm)
Weight: 7.5 lb. (3.4 Kg)
Range*
Sensitivity Range Standard
1 (Low)
16.5 ft ( 5 m)
-
2 (High)
50 ft (15 m)
2.4 ft (0.75 m)
* The minimum distance from the detector is 20 inches (50cm)
* At extreme temperatures - 15% Max. Reduction in range