beautypg.com

Spectrex 20/20R - Single IR Flame Detector User Manual

Page 45

background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

37

8.5 Maintenance Records
It is recommended to record maintenance operations performed on a detector in a
system Log-book. The record should include information, which identifies the unit,
the installation date, contractor, and entries for every maintenance operation
performed including the description of the operation, date and personnel ID. If a
unit is sent to the manufacturer or distributor for service, a copy of the
Maintenance records should accompany it.

8.6 Troubleshooting

8.6.1 Fault Indication
1 Check power supply for correct voltage, polarity and wiring.

2 Check detector window and reflector for cleanness. If necessary clean the

window as indicated in paragraph 8.3 and repeat the test.

3 Disconnect the power supply to the system and check the detector's internal

wiring.

4 Reconnect power supply and wait approximately 60 seconds. Repeat the test.

If the indication LED is still flashing, the unit requires service.

8.6.2 False Alarm or Warning Indication

1 Disconnect the power supply from the system and check internal wiring.

2 Reconnect power supply and wait approximately 60 seconds. If indication

remains, the unit requires service.