beautypg.com

Spectrex 20/20R - Single IR Flame Detector User Manual

Page 36

background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

28

6.7 Terminal wiring (See Fig. No.10 and No.11.)
The detector contains a Terminal Board consisting of two (2) terminal blocks (Item
4). The left terminal block is labeled 1 to 7, the right terminal block is labeled 8 to
14.

The following describes the function of each electrical terminal of the
detector:

Power Supply (Terminal Numbers 1, 2):

Input power - Terminal No. 1.
The RETURN - Terminal No. 2.

Manual Bit Activation (Terminal No. 3):

Terminal No. 3 is used for the Manual BIT activation. The manual BIT is
initiated by a momentary connection of Terminal No. 3 to the power supply
Return line (terminal 2).

Fault Relay

(Terminal Numbers 4, 5):

The Fault output is N.O. SPST relay at Terminals No. 4 and 5. The contacts
are closed when the detector is in its normal operational condition.

Alarm Relay (Terminal Numbers 6, 7, 8):

The Alarm output is a change over contact relay (SPDT).
Terminal No. 6 is the N.O. relay contact.
Terminal No. 7 is the COMMON relay contact.
Terminal No. 8 is the N.C. relay contact.


Accessory Relay (Terminal Numbers 9, 10):

The Accessory output is N.O. SPST relay at Terminals No. 9 and 10.
The Accessory relay may act in parallel with the ALARM relay to activate
another external device or it may provide a warning signal, depending on the
position of SW1-2.

Note

To protect the dry contacts from voltage surges when connected to reactive
loads (electric motors, sirens, etc.), connect an appropriate varistor over these
contacts.