beautypg.com

Spectrex 20/20R - Single IR Flame Detector User Manual

Page 27

background image

Spectrex Inc. - SharpEye

TM

Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005

19

E. Electrical outputs

Dry Contact Relays:

Table 10: Contact Ratings

Relay
Name

Type

Normal
position

Maximum Ratings

Alarm

SPDT N.O. N.C. 2A at 30VDC or 0.5A at 250 VAC

Accessory SPST N.O.

5A at 30VDC or 250 VAC

Fault

SPST N.C.

5A at 30VDC or 250 VAC

4-20mA Current Output:

Terminals 11 and 12:

FAULT

< 2mA

(Typical 0)

NORMAL

4 - 6mA

( 5)

WARNING

9 - 11mA

(10)

ALARM

14 –16mA

(15)

Communication Network:

The detector is equipped with an RS-485 communication link that can
be used in installations with computerized controllers.

Figure 7: Flame Detector Assembly - Schematic Section