Single IR Flame Detector Manual – TM 20/20R, Rev. A January2005
4
3. Performance
3.1 Detection Sensitivity
Detection sensitivity is the maximum distance at which the detector will reliably
detect a specific size of fire & typical type of fuel (standard fire).
Standard Fire:
A 1ft x 1ft (0.3m x 0.3m) Gasoline pan fire with max. wind speed of 6.5 ft/sec
(2 m/sec).
Sensitivity Ranges:
The detector has two user selectable sensitivity ranges. For each range there are
two response levels.
1. WARNING (Pre-alarm)
2. ALARM
The detection distance, for the WARNING level, is approximately 10% higher than
the ALARM distance. Alarm response times for a “standard fire” at a specified
range are shown hereunder.
Table 1: Alarm Response Time Versus Range
Sensitivity
1
2
Range – ft (m)
15 (5)
50 (15)
Response Time (sec)
5 10
For some typical ambient conditions the Zeta parameter as defined in NFPA 72 for
the detector is 0.005 (1/meter).
Note:
Zeta parameters may vary significantly with changes in temp, air pressure,
humidity, visibility conditions, etc.