UV/IR Flame Detector Manual – TM20/20LB Rev E, August 2004

48

Figure 14: UV/IR Detector Target Point

C

C

a

a

u

u

t

t

i

i

o

o

n

n

:


1 The following test will simulate a real fire condition and may activate the

extinguishing system or other alarms. If this is not desired, disconnect them
before the test and reconnect after the simulation.

2 Please note that if your flame detector mode is in “High UV protection

enabled” - switch SW-3 ON, a beam collimator should be used.


Follow these instructions to simulate a fire:

1 Aim the Fire Simulator towards the detector’s “Target Point” (see Fig. 14)

2 For testing, keep a distance of at least 20 inches (50cm) from the detector.

3 Press the operation button once. Fire simulation will last for 20 seconds. The

detector will send an alarm signal.

4 For another fire simulation a 20 second time lapse is required between tests.

5 Make sure the optical window is clean and keep the Fire Simulator in the

storage case when not in use.