7 terminal wiring (figures 6,7) – Spectrex 20/20L (LB) - UV/IR Flame Detector User Manual

Page 36

background image

Spectrex Inc. - SharpEye

TM

UV/IR Flame Detector Manual – TM20/20LB Rev E, August 2004

28

6.7 Terminal Wiring (Figures 6,7)

The detector contains a terminal board consisting of two terminal blocks.
The left terminal block is labeled 1 to 6; the right terminal block is labeled 7 to 12.
See Figure 6.

The following describes the function of each electrical terminal of the detectors.

Power Supply:

(Terminals 1, 2)

Input power is supplied to terminal No. 1.
The RETURN is connected to terminal No.2.

Manual Bit Activation: (Terminal 3)
Terminal No. 3 is used for the manual BIT activation. The manual BIT is initiated
by a momentary connection of Terminal No. 3 to the power supply return line.

Alarm Relay:

(Terminals 4, 5, 6)

The Alarm output is a change over contact relay (SPDT)
Terminal No. 4 is the NO relay contact
Terminal No. 5 is the COMMON relate contact
Terminal No. 6 is the NC relay contact

Fault Relay

: (Terminals 7, 8)

The Fault output in NC SPST contact at terminals no. 7 and 8. The contacts are
closed when the detector is in its normal operational condition

Accessory Relay

: (Terminals 9, 10)

The Accessory output is N.O. SPST relay at terminals no. 9 and 10. The
Accessory relay may act in parallel with the Alarm relay to activate another
external device or it may provide a warning signal, depending on the position of
SW1-4.

Note

To protect the dry contacts from voltage surges when connected to
reactive loads (electric motors, sirens, etc.) connect an appropriate
varistor over these contacts.



4-20mA Output: (Terminals11, 12)
As specified in section 5.1.e.
Terminal 11 is used as RETURN terminal (-) (RTN)
Terminal 12 is used as output terminal (+)
See appendix B for more details.