4.3 Mode Selection

The detector has 2 DIPswitches, which enables the user to adapt the detector’s
operation to specific applications:

• Function switch (SW1)

• Alarm Delay Switch (SW2)

4.3.1 Function switch (SW1)
The user can select the desired mode of operation by means of this switch
according to Table 4.

Table 4. Function Switch SW1

SW ON Position

OFF Position

1

Alarm Signal Latching enabled.
Reset of the Alarm signal is
performed by momentary
disconnection of power supply or
manual BIT activation.

Alarm Signal Latching disabled
(default).

2

Automatic & Manual BIT can be
performed (default).

Only Manual BIT can be
performed.

3

High UV protection enabled.

High UV protection disabled
(default).

4

Accessory Relay used by the
Warning level.

Accessory Relay used in parallel to
the Alarm Relay (default).

5

Warning conditions: UV & IR at
Warning level, or UV at high level.

Warning conditions:
UV & IR at Warning level (default).

6

Following a successful Manual BIT
sequence:
Alarm Relay is activated and the
4-20mA output turns to 20mA for
approximately 3 seconds (default).

Following a successful Manual BIT
sequence

(1),(2)

:

Alarm Relay is not activated

7

Following a successful Manual BIT
sequence

(2)

:

Accessory Relay is activated and the
4-20mA output turns to 16mA for
approximately 3 seconds

(3)

(default).

Following a successful Manual BIT
sequence

(2)

:

Accessory Relay is not activated.

8

Accessory Relay used as EOL relay. Accessory Relay function in

accordance with the position of
SW1-4 (default).


Notes

:

1 The BIT sequence may last up to 7 seconds. Verify that all eight (8) switches

are in the appropriate setting (ON/OFF), to achieve the required functional
mode of operation.

2 SW1-2, SW1-6, SW1-7 are function only for model 20/20LB. Model 20/20L

does include BIT.

3 If both SW1-6 and SW1-7 are at on position the 4-20mA output is 20mA

(Alarm Level) after successful manual BIT.