e. Electrical Outputs

:

Output Relays:

Table 7. Dry Contacts Relays Ratings

Relay
Name

Type

Normal position

Maximum Ratings

Alarm

SPDT

N.O. N.C.

2A at 30VDC or 0.5A at 250 VAC

Accessory SPST

N.O.

5A at 30VDC or 250VAC

Fault

SPST

N.C.

5A at 30VDC or 250 VAC

4-20mA Current Output stepped Levels at different detector states (on

terminals 11 and 12):

Fault: 0mA

+0.5mA

Bit Fault:

2mA

±10%

Normal: 4mA

±5%

IR Detection:

8mA ±5%

UV Detection: 12mA

±5%

Warning: 16mA

±5%

Alarm: 20mA

±5%

o

The 4-20mA output is a current source type. The signal is driven via
terminal 12 through the load to terminal 11 that should be at RTN
level (when connected to terminal 2)

o

Maximum load permitted resistance for the 4-20mA is 600 ohm.