beautypg.com

Operation – Spectrex 20/20L (LB) - UV/IR Flame Detector User Manual

Page 19

background image

Spectrex Inc. - SharpEye

TM

UV/IR Flame Detector Manual – TM20/20LB Rev E, August 2004

11

4. Operation

4.1 Visual Indications

Two indication LEDs are located in the detector’s front window.

Yellow LED - Provides indication of Normal or Fault state.
Red LED

- Provides indication of Warning or Alarm state.


Table 3. LED indications within different detector states

Detector State

Yellow LED

Red LED

Normal

Blink at 0.5Hz Rate

Off

Fault or BIT Fault

Blink at 2Hz Rate

Off

Warning

Blink at 0.5Hz Rate

Blink at 2Hz Rate

Alarm

Blink at 0.5Hz Rate

On

Warning at BIT Fault Blink at 2Hz Rate

Blink at 2Hz Rate

Alarm at BIT Fault

Blink at 2Hz Rate

On

4.2 Output Signals

The detector includes the following control outputs:

• Alarm Relay

• Accessory Relay

• Fault Relay

• 4-20mA Current Source Output