Measurement setting, Recording setting, Save setting – KYORITSU 6315 Quick Manual User Manual
Page 39

Setting (SETUP)
KEW6315
- 37 -
KEW6315
Measurement setting
Setting item
Details of setting
Demand
Interval
Not be used/ 10min/15min/30min
Inspection
cycle
Interval: 10min/ 15min
1min/2min/5min
Interval: 30min
1min/2min/5min/10min/15min
Target
0.001mW-999.9TW(100.0kW)
Harmonics
THD(total harmonic distortion) calc.
THD-F(based on the fundamental waveform)/
THD-R(based on all rms values)
Allowable range
Default/ customize(V/A)
MAX HOLD
ON/OFF
Power quality
Hysteresis
against nominal V: 1 to 10%(5%)
Transient
against nominal V: ±50 to ±2200Vpeak(300%)
Swell
against nominal V: 100 to 200%(110%)
Dip
against nominal V: 0 to 100%(90%)
Int
against nominal V: 0 to 100%(10%)
InrushCurrent
against “A” range: 0 to 110%(100%)
Flicker
Filter (Ramp)
230V/220V/120V/100V
Capacitance
calculation
Target PF
0.5-1(1.000)
Recording setting
Setting item
Details of setting
Recording
item
Harmonics
Record/ Do not record
Power quality (event)
Record/ Do not record
Recording
method
Interval
1sec/2sec/5sec/10sec/15sec/20sec/30sec/
1min/2min/5min/10min/15min/20min/30min/
1hour/2hours/150,180 cycles (approx 3sec)
Start
Manual/Constant rec./Time period rec.
Constant
measurement
REC Start
Day/ Month/ Year Hour: Minute (00/00/0000 00:00)
REC End
Day/ Month/ Year Hour: Minute (00/00/0000 00:00)
Timer
Rec. period
Start-End
Day/ Month/ Year (DD/MM/YYYY)- Day/ Month/ Year (DD/MM/YYYY)
Time period
Start-End
Hour: Minute (hh:mm)- Hour: Minute (hh:mm)
* Default values are highlighted in gray.
Save setting
Setting item
Details of setting
REC data
Delete data.
Transfer data.
Format
KEW6315 setting
Save setting.
Read settings.