beautypg.com

Earth resistance measurement, 1 principle of measurement – KYORITSU 4300 User Manual

Page 17

background image

̶ 15 ̶

8. Earth resistance measurement

This instrument can measure the earth resistances of distribution

line, internal wiring and electrical appliance.

#

DANGER

● Never apply inputs exceeding 300V between the measuring

terminals at earth voltage measurements.

● No voltage should be applied between the measuring terminals

during earth resistance measurements.

8-1 Principle of measurement

This instrument carries out earth resistance measurements based

on the fall-of-potential method. This is a simplified earth resistance

tester and uses the existing earth systems (with a sufficiently

low earth resistance) such as buried metal pipes like main water

pipe, common earth for commercial power supply and a lightning

electrode on buildings and performs measurements based on the

2-pole measurement method.
The AC constant current

I” is applied between the

measurement object “

Rx

(earth electrode) and the

existing electrode “

re” to

obtain the earth resistance

value “

Rx + re” and find out

the voltage “

V” between the

E and H+S(C+P) terminals.

See Fig. 8-1.
Rx + re = V / I
The resistance “

re” of the existing earth electrode with which

H+S(C+P) terminal is connected is added to the true resistance

Rx” of the measured object, and displayed as the measured result.

Re (measured value) = Rx + re

If the value of “

re” is already known, deduct it from the measured

value “

Re” to determine “Rx” value.

Rx (true resistance value) = Re – re

H+S (C+P)

terminal

E

terminal

Voltmeter

Earthing system

under test

Earth electrode

Constant current

generator

Secondary

Primary

I→

Fig. 8-1