3.Specifications

Measuring Range and Accuracy (at 23±5°C, relative humidity 45-75%)

Insulation Resistance Ranges:(IEC 61557-2)

Normal output
Voltage

250V

500V

1000V

Measuring Ranges

0 - 100M

0 - 200M

0 - 400M

Open -Circuit

Rated test voltage +20%, -0%

Voltage
Normal current

1mA DC +20%, -0%

Short -Circuit

About 1.3mA DC

Current
Accuracy guaranteed

0.1-10M

0.2-20M

0.4-40M

range

Accuracy

±5% rdg at Accuracy guaranteed ranges
±0.7% of scale length at ranges other than above ranges

Continuity Test (Resistance Test) Ranges:(IEC 61557-4)

Ranges

3

500

Open -Circuit Voltage

About 4.1V DC

Measuring Current

Greater than 200mA

Accuracy

±1.5% of scale length at other measuring ranges

Operating Error

Insulation Resistance Ranges(IEC 61557-2)

Ranges

Measuring range to keep

Maximum percentage

operating error

operating error

250V/100M

0.1M

- 10M

500V/200M

0.2M

- 20M

±30%

1000V/400M

0.4M

- 40M

― 5 ―

2.Features

MODEL-3132A is an analogue tester with five ranges for insulation resistance
measurement and continuity testing (resistance tests) of low voltage
installations.

Designed to safety standards:

IEC 61557-1 (General requirements for measuring equipment for low

voltage distribution systems)

IEC 61557-2 (Equipment for insulation resistance measurement for low

voltage distribution systems)

IEC 61557-4 (Equipment for resistance tests for low voltage distribution

systems)

Dust and drip proof construction to IP54.
Three insulation test ranges : 250V/100M

,500V/200M

,1000V/400M

.

Two continuity test ranges : 3

,500

AC voltage warning measurement can be made on all ranges without

depressing the test button.

Easy for battery check.
When the test button is released any charge stored in the circuit under test

is automatically discharged.

Remaining electric charges can be observed on AC voltage warning range.
LIVE circuit audible and visual indication.
Fuse protected.
Color coded scales and range switch position for easy reading.
Uses only 6 x 1.5V battery type R6P,1.5V AA or equivalent.

― 4 ―

3132A-E/03-08 03.8.6 10:33 AM ページ 4