4.Instrument Layout

METER MOVEMENT ZERO ADJUST

TEST BUTTON

SCALE PLATE

INPUT CONNECTOR

LIVE CIRCUIT LAMP

OHMS ZERO ADJUST

RANGE SELECTOR SWITCH

TEST PROBE (RED) LINE PROBE

TEST PROBE (BLACK) EARTH PROBE

TEST PROBE CAP(RED)

TEST PROBE CAP(BLACK)

ALLIGATOR CLIP(BLACK)

― 8 ―

5.Preparation for Testing

5-1 Mechanical Zero Adjustment

Check that the pointer lines up with the middle of the mark on the scale correctly.
If not, adjust it by rotating the meter movement zero adjust with a screwdriver, etc.

5-2 Battery Voltage Check

Set the range selector switch to BATT. CHECK position.
Press the test button.
Then the pointer deflects. Judge the battery status with BATT.GOOD

mark on the scale plate.
If the pointer does not move to BATT.GOOD mark, the batteries are
exhausted. Replace them with new batteries according to section 8 for
battery & fuse replacement.

5-3 Test Probe Connection

Insert the test probe fully into the terminal of the instrument.
Connect the earth clip of the test probe (black) to EARTH terminal and the
line probe (red) to LINE terminal of the connector terminal.

5-4 Test Probe Check

Set the range selector switch to 3

position and press and turn the Test

button to lock it down.
When the test probe are connected together, the pointer should move from
the

position towards the 0 position on the blue ohms scale. If not, the

probe or fuse may be faulty.
Release the Test button after completion.

WARNING

When the test button is pressed with the range selector switch in the

megaohm range position,take care not to touch the tip of the test probe

where a high voltage is present in order to avoid possible shock hazard.

CAUTION

Do not keep the test button pressed or locked by turning it clockwise

during battery check.

― 9 ―