Installation and operating instructions BM 702 (06/04)

When using the PTFE Wave-Stick in hazardous areas of Zone 0, any electrostatic charging of
the stick, e.g. by flow of product, must be avoided!

3 Electrical

connection

To open the signal converter, please use a screwdriver and release the four visible screws
on top of the blue housing.

Terminal assignment
BM 702:





The polarity of the 4-20 mA connection
is arbitrary.

FE

1

2

4-20mA

current-

loop

cable gland


Equipotential bonding
When used in hazardous areas, the BM 702 Ex can be incorporated in the PA
equipotential bonding system
, e.g. by using the separate U-clamp terminal at the “neck“
of the BM 702 Ex.

Rated temperature of connecting cables: see Section 6.

Supply voltage at the terminals (1,2)
The 4-20 mA supply must be able to provide the following voltage U at the terminals of the
BM 702 – dependent on the current I. Please consider also the line resistance and possible
loads on the secondary side of the supply unit.

4mA

12mA

8mA

16mA

20mA

3.6mA

22mA

I

U

13V

14V

15V

16V

17V


The allowed upper limit R for load+line resistance is depending on the specification of the
supply unit:
U at 20mA (supply unit)

14 V

15 V

16 V

17 V

18 V

Max. resistance R

50

Ω 100

Ω 150

Ω 200

Ω 250