Simply scaling the current output

1) Drain the tank completely to the 0% marking (= 4 mA)

1)

.


2) Press the lower keys (

↵ und ↓) down, until the

asterisks on the display „TANKHEIGHT|********“ are
replaced by the actual measured distance value

2)

.

3) Then release and press

↵. In the lower line: „SURE

NO?“ is displayed.

4) If this value is not plausible or the tank is not empty,

abort by

↵. Or accept the value by pressing ↑ (“SURE

YES?”) and then

↵.



5) Now the tank height is set.


6) In the next step you can also enter this value as 4 mA

scaling (0%). Press

↵. In the lower line now: „SURE NO?“

is displayed again.

7) If this value shall not be stored, abort by

↵. Or accept

this 4mA scaling by pressing

↑ (“SURE YES?”) and then

↵.

8) Fill the tank to the 100% mark. Use the same
procedure for the 100% point = 20 mA only now by

pressing the top keys

→ and ↑

1)

2)

.


9) First the measured distance can be taken as block distance. After
this you can enter or adjust the 20 mA point (100%) according to
the actual level.

1)

This example was written for the case: current output = level (default). For distance measurement the

points 0% (short distance = high level) and 100% (large distance = low level) are exchanged

2)

If no reliable measurement is possible „NO ACCESS“ is displayed. Abort by pressing