Technical data – KROHNE BATCHFLUX 5500 C EN User Manual
Page 24
6
TECHNICAL DATA
24
BATCHFLUX 5500 C
www.krohne.com
05/2014 - 4000827703 - HB BATCHFLUX 5500 R03 en
Operating conditions
Temperature
Temperature
Temperature
Temperature
Process temperature
Dependent on ambient temperature. See chapter "Temperatures".
Cleaning temperature
SIP: Maximum 1 hour at 150°C / +302°F
CIP: Maximum 1 hour at 140°C / +284°F
Shock
≤ 3 K/s
Ambient temperature
-40…+60°C / -40…+140°F
Storage temperature
-50…+70°C / -58…+158°F
Pressure
Pressure
Pressure
Pressure
Ambient
Atmospheric
Process pressure
up to 16 bar / 232 psi for DN10...15
up to 40 bar / 580 psi for DN2.5...6 / DN25...40
Vacuum load
0 mbara / 0 psig
Chemical properties
Chemical properties
Chemical properties
Chemical properties
Physical condition
Liquids
Electrical conductivity
≥ 5 μS/cm (≥ 20 μS/cm for demineralised water)
Recommended flow velocity
-12...+12 m/s / -39...+39 ft/s
Installation conditions
Installation
For detailed information see chapter "Installation".
Inlet run
≥ 5 DN
Outlet run
≥ 2 DN
Dimensions and weights
For detailed information see chapter "Dimensions and weights".
Materials
Sensor- and converter housing
Stainless steel 1.4404 / 1.4408
Measuring tube
Fused in-place
Measuring electrodes
DN2.5...15: Cermet
DN25...40: Platinum
Process connections
Connection
Sandwich design
Optional: Pressure relief groove at flange facing of the sensor
Construction drawings of recommenced counter flanges are
available from download centre.