beautypg.com

Electrical connections – KROHNE OPTIFLEX 1300 IECEx User Manual

Page 12

background image

3

ELECTRICAL CONNECTIONS

12

OPTIFLEX 1300 C

www.krohne.com

09/2010 - 4000176402 - AD IECEX OPTIFLEX1300 R02 en

3.1 General notes

3.2 Terminal compartment

3.2.1 How to open the terminal compartment

• De-energize the circuit.
• After the time given in the table that follows, remove the cover stop 1.

i

Use a 3 mm allen wrench.

• Remove the terminal compartment cover 2.

Time necessary to de-energize an Ex d[ia]- or Ex tD[iaD]-approved device

WARNING!

De-energize the circuit.

Use the applicable cable glands for the cable entry openings in the housing (M20×1.5 or

½

NPT). For the cable entry size, refer to the device nameplate.

If ambient temperature >70

°

C / >158

°

F, use heat-resistant cables, cable glands and cable

entry plugs certified for continuous operation above +80

°

C / +176

°

F.

Figure 3-1: How to open the terminal compartment

1 Cover stop
2 Terminal compartment cover

WARNING!
Do not remove the terminal compartment cover while the electrical power is connected.

Temperature class

Time to de-energize the Ex d[ia]- or Ex tD[iaD]-

approved device

[minutes]

T6

20

T5

10

T4, T3, T2

Not necessary